Danfoss IPS 8 Technical Data, Installation And Use page 24

Intelligent purging system for ammonia
Hide thumbs Also See for IPS 8:
Table of Contents

Advertisement

User Guide | Intelligent Purging System (IPS 8) for Ammonia - Technical data, installation and use
Register Parameter Name
8154
Val6
8155
Val7
8156
Val8
8157
RangedVal
8158
TempStatus
8159
BPLStatus
8160
BPHStatus
8161
DisTemp
8162
SuctionTemp
8163
TshValveStatus
8164
TshCalculate
ALARMS
1901 .08
General alarm
1901 .09
Temp Sensor Fault
1901 .10
BPL Sensor Fault
1901 .11
BPH Sensor Fault
1901 .12
Low temperature
1901 .13
Hi temperature
1901 .14
Low pressure BPL
1901 .15
Hi pressure BPL
1901 .00
Low pressure BPH
1901 .01
Hi pressure BPH
1901 .02
System is OFF
1901 .03
Memory is full
1901 .04
Totla purge time error
1901 .05
Compressor EROR
1901 .06
Liquid alarm
1901 .07
Memory wrong!
24 | BC306932151284en-000201
User
Description
Level
This indicates if the
0
purge point is active
This indicates if the
0
purge point is active
This indicates if the
0
purge point is active
This indicates if the
0
ICFD valve is active
The measured
temperature on the
0
discharge line of
compressor
The pressure on R452
0
The pressure on R717
0
The measured
temperature on the
0
purge valve
The measured
temperature on the
0
suction line
The measured value of
0
the superheat
The calculated value
of the superheat from
0
the refrigerant type
Input from AI3. Leads
0
to shut down of IPS 8
Indicates no signal
from temperature
0
R452A sensor
Indicates no signal
from pressure sensor
0
(R452a)
Indicates no signal
from pressure sensor
0
(R717)
Indicates too low
ambient temperature
0
(<-10 °C)
Indicates too high
ambient temperature
0
(>120 °C)
Indicates too low
0
R452a pressure
Indicates too high
0
R452a pressure
Indicates too low R717
0
pressure
Indicates too high
0
R717 pressure
Indicates status o the
0
main switch
A memory reset is
0
required
This occurs when PLT
is activated. System
will automatically
0
restart when CST has
expired
Indicates no status is
being received from
0
KL01
Signal from the LLS
that there is liquid in
0
the evaporator
Wrong counter
values. The unit will
0
automatically repair
itself
Default
Min Value
Max Value
Value
-32768
32767
0
-32768
32767
0
-32768
32767
0
-32768
32767
0
-32768
32767
0
-32768
32767
0
-2147483648
2147483647
0
-32768
32767
0
-2147483648
2147483647
0
-32768
32767
0
-2147483648
2147483647
0
0
1
0
0
1
0
0
1
0
0
1
0
0
1
0
0
1
0
0
1
0
0
1
0
0
1
0
0
1
0
0
1
0
0
1
0
0
1
0
0
1
0
0
1
0
0
1
0
Modbus
Unit/
Read/
Modbus
Function
Type
Write
Data Type
Code
Read
N/A
3
Short
only
Read
N/A
3
Short
only
Read
N/A
3
Short
only
Read
N/A
3
Short
only
Read
°C
3
Short
only
Read
bar
3
Short
only
Read
bar
3
Short
only
Read
°C
3
Short
only
Read
°C
3
Short
only
Read
°C
3
Short
only
Read
K
3
Long
only
Read
AUTO R.
3
Long
only
Read
AUTO R.
3
Long
only
Read
AUTO R.
3
Long
only
Read
AUTO R.
3
Long
only
Read
AUTO R.
3
Long
only
Read
AUTO R.
3
Long
only
Read
AUTO R.
3
Long
only
Read
AUTO R.
3
Long
only
Read
AUTO R.
3
Long
only
Read
AUTO R.
3
Long
only
Read
AUTO R.
3
Long
only
Read
AUTO R.
3
Long
only
Read
AUTO R.
3
Long
only
Read
AUTO R.
3
Long
only
Read
AUTO R.
3
Long
only
Read
AUTO R.
3
Long
only
© Danfoss | DCS (ms) | 2020.01
Persistent
Yes/No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No