User Guide | Intelligent Purging System (IPS 8) for Ammonia - Technical data, installation and use
Configuring using the LCD
Table 02
Main menu navigation
Main Menu
Submenu
Submenu/status Submenu/status
No alarm
Active alarms
up to 15 alarms
(see table
below)
Alarms
Reset alarms
Log history
Clear log
history
Login
Password
Turn On
Start
Turn Off
Parameters
Unit config
Input/Output
18 | BC306932151284en-000201
By pressing
the main menu will show up with the options below
***
Compressor
Limits settings
Min
Max
Default Description
Up to 15 possible alarms listed by arrow up/down
Reset all actual alarms
View log history
Clear log history
200
N/A
Main swith ON
Main swith OFF
0 sec
100 sec
20 sec
SDT (Compressor start delay)
2000
5 min
45 min
PDT (Pull down time)
min
2000
1440
180 min
CST (Cycle time)
min
min
768
160
24 hours
PLT (Endless purging max time)
hours
hours
0 bar
5 bar
0.5 bar
Comp Diff (Hysteresis min allowed ammonia pressure)
0 bar
12 bar
6.5 bar
Setpoint (Min allowed ammonia pressure)
Input / Output Display & Config
Label
CM2
CM3
CM4
VA5
CM5
CM1