closed down unintentionally. The IE-CS(T)-2TX-xRS232/485 will then force the existing TCP connection to
close.
ATTENTION
The Inactivity time should be configured to be larger than the Force transmit timeout setting. To prevent
the unintended loss of data due to the session disconnection, it is highly recommended that you set this value
large enough so that the intended data transfer is completed.
ATTENTION
Inactivity time is ONLY active when TCP connect on is set to Any character.
Ignore jammed IP
Setting
No or Yes
By default, when Max connection is greater than 1, and the serial device is transmitting data, if any one of the
connected hosts is not responding, it will wait until the data has been transmitted successfully before
transmitting the second group of data to all hosts. If you select Yes for Ignore jammed IP, the host that is
not responding will be ignored, but the data will still be transmitted to the other hosts.
Packing length
Setting
0 to 1024
Default = 0, The Delimiter Process will be followed, regardless of the length of the data packet. If the data
length (in bytes) matches the configured value, the data will be forced out. The data length can be configured
for 0 to 1024 bytes. Set to 0 if you do not need to limit the length.
Delimiter 1
Setting
00 to FF (hex)
Delimiter 2
Setting
00 to FF (hex)
Once the IE-CS(T)-2TX-xRS232/485 receives both delimiters through its serial port, it immediately packs all
data currently in its buffer and sends it to the IE-CS(T)-2TX-xRS232/485's Ethernet port.
ATTENTION
Delimiter 2 is optional. If left blank, then Delimiter 1 alone trips clearing of the buffer. If the size of the serial
data received is greater than 1 KB, the IE-CS(T)-2TX-xRS232/485 will automatically pack the data and send
it to the Ethernet. However, to use the delimiter function, you must at least enable Delimiter 1. If Delimiter
1 is left blank and Delimiter 2 is enabled, the delimiter function will not work properly.
Factory Default
No
Factory Default
0
Factory Default
None
Factory Default
None
5-20
Web Console Configuration
Necessity
Optional
Necessity
Optional
Necessity
Optional
Necessity
Optional