Inspection/Cleaning Of The Burner Assembly
20.
Most of the particulate matter in the combustion air stream should be caught by a pre-filter or
cyclone. However it is necessary to pull the burner head once a year, and inspect and clean it
Remove Burner
Remove the bolts holding the air duct to the burner plate and the fan.
Lift the air duct straight up. Be mindful not to lose the gasket that seals the transition to the
burner plate.
You should now be able to lift the burner straight out of the burner plate.
Inspect and Clean the Burner
The burner should be clean and free of dust.
This can be accomplished using compressed air. Blow compressed air through the mesh
from the outside in, then empty any contaminates inside the burner can.
Inspect the burner signs of local overheating or soot. If soot is present, either the pilot or
the main burner has incomplete combustion. The combustion controls should be
checked, while local overheating will result in discoloured mesh or possible detachment
or sagging. The condition of the insulting heat barrier should also be checked.
Flush boiler if necessary. More extensive cleaning may be required; consult a local water
21.
chemistry expert for recommendations.
AFTER ALL REPAIRS & MAINTENANCE - IN ADDITION
6.8.6
1. Complete all safety checks in the daily and weekly maintenance section.
2. Fire the boiler and perform combustion safety checks.
3. Analyse combustion throughout the range and verify proper operation of safety devices.
VSRT-IOMM-2019-1
MAINTENANCE - 6
Page 69