120 Control units of the converter

Layout and connections

BCU layout and connections

Description
I/O
I/O terminals (see the following diagram)
SLOT 1
I/O extension, encoder interface or
fieldbus adapter module connection.
(This is the sole location for an FDPI-02
diagnostics and panel interface.)
SLOT 2
I/O extension, encoder interface or
fieldbus adapter module connection
SLOT 3
I/O extension, encoder interface, fieldbus
adapter connection
SLOT 4
RDCO-0x DDCS communication option
module connection
X205
Memory unit connection
BATTERY
Holder for real-time clock battery
AI1
Mode selector for analog input AI1
(I = current, U = voltage)
AI2
Mode selector for analog input AI2
(I = current, U = voltage)
D2D TERM Termination switch for drive-to-drive link
(D2D)
DICOM=
Ground selection. Determines whether
DIOGND
DICOM is separated from DIOGND (ie,
the common reference for the digital
inputs floats).
7-segment display
Multicharacter indications are displayed as repeated
sequences of characters
("U" is indicated briefly before "o".)
Control program startup in progress
(Flashing) Firmware cannot be started.
Memory unit missing or corrupted
Firmware download from PC to control
unit in progress
At power-up, the display may show short
indications of eg. "1", "2", "b" or "U".
These are normal indications immediately
after power-up. If the display ends up
showing any other value than those
described, it indicates a hardware failure.