Electrical Safety In Installation, Start-Up And Maintenance; Precautions Before Electrical Work - ABB ACS880-87LC-4000A/4021A-7 Hardware Manual

Wind turbine converters
Table of Contents

Advertisement

Note:
Only authorized persons are allowed to repair a malfunctioning converter.

Electrical safety in installation, start-up and maintenance

Precautions before electrical work

These instructions are for the qualified electricians who do work on the converter,
generator cable or generator.
WARNING! Perform the electrical safety precautions below before starting any
work on the installation. If you ignore the precautions, physical injury or death, or
damage to the equipment can occur. If you are not a qualified electrician, do not
proceed or do any installation or maintenance work.
1. Clearly identify the work location.
2. Disconnect all possible voltage sources.
Open the main circuit breaker (Q1), disconnect, lock and attach a warning notice
to it. See section
Open the charging circuit switch-disconnector (Q10). See section
the charging circuit from the main circuit
Open and lock out the auxiliary voltage switch-disconnectors (Q2 and Q3). See
section
Disconnecting the external auxiliary power supply
Disconnect any external dangerous voltages from the control circuits (such as
relay outputs).
Open, disconnect and lock out the breaker of the grid transformer as the main
circuit breaker of the converter does not remove the voltage from the grid cable
busbars and some auxiliary circuits. Attach a warning notice to the disconnector.
Lock the turbine rotor (and generator shaft).
Open the safety switch between the generator-side converter and the generator (if
any).
After you disconnect the converter, always wait for five minutes to let the
intermediate circuit capacitors discharge before you continue.
3. Protect any other energized parts in the work location against contact.
4. Take special precautions when close to bare conductors.
5. Measure that the installation is de-energized.
Use a multimeter with an impedance of at least 1 Mohm.
Make sure that the voltage between the converter grid cable terminals (L1, L2, L3)
and the grounding (PE) busbar is close to 0 V.
Make sure that the voltage between the generator cable terminals (U2, V2, W2)
and the grounding (PE) busbar is close to 0 V.
Make sure that the voltage between the DC bus and the grounding (PE) busbar is
close to 0 V.
Opening and disconnecting the main circuit breaker
Safety instructions 13
on page 19.
on page 20.
on page 16.
Disconnecting

Advertisement

Table of Contents
loading

This manual is also suitable for:

Acs880-87lc-4000a/4132a-7Acs880-87cc

Table of Contents