Placing the converter
The cabinet can be placed into its final position with an iron bar and a wooden piece at the
bottom edge of the cabinet. Place the wooden piece carefully to avoid damage to the
cabinet frame.
The cabinet has a back-to-back design, and thus you cannot install it with a longer side
against a wall.
The converter must be installed in an upright vertical position.
Notes:
•
Leave a 400 mm (16 in) clearance above the converter cabinet to allow pressure
release lids to open in an arc fault situation.
•
Leave space at the side for the coolant pipes.
•
You can adjust the height, for example, if the floor is uneven by using metal shims
between the cabinet frame and floor.
> 400 mm (16 in)
Mechanical installation 49