Default I/O Connections - ABB ACS580-01 Manual

Hide thumbs Also See for ACS580-01:
Table of Contents

Advertisement

32 EN – R1...R4 Quick installation guide

Default I/O connections

Default I/O connections of the ABB Standard macro are shown below.
R1-
1...10 kohm
R4
R5
R6-
max.
500 ohm
R9
EN
DA
DE
ES
FI
FR
IT
NL
PL
PT
RU
SV
Total load capacity of the Auxiliary voltage output +24V (X2:10) is 6.0 W (250 mA / 24 V DC).
Wire sizes:
TR
2
0.2...2.5 mm
(24...14 AWG): Terminals +24V, DGND, DCOM, B+, A-, DGND, Ext. 24V
2
0.14...1.5 mm
ZH
Tightening torques: 0.5...0.6 N·m (0.4 lbf·ft)
X1
Reference voltage and analog inputs and outputs
1
2
3
4
5
6
7
8
9
X2 & X3
Aux. voltage output and programmable digital inputs
10
11
12
13
14
15
16
17
18
X6, X7, X8 Relay outputs
19
20
21
22
23
24
25
26
27
X5
EIA-485 Modbus RTU
29
30
31
S4
S5
X4
Safe torque off
34
35
36
37
38
(26...16 AWG): Terminals DI, AI, AO, AGND, RO, STO
SCR
Signal cable shield (screen)
AI1
Output frequency/speed reference: 0...10 V
AGND
Analog input circuit common
+10V
Reference voltage 10 V DC
AI2
Not configured
AGND
Analog input circuit common
AO1
Output frequency: 0...20 mA
AO2
Output current: 0...20 mA
AGND
Analog output circuit common
+24V
Aux. voltage output +24 V DC, max. 250 mA
DGND
Aux. voltage output common
DCOM
Digital input common for all
DI1
Stop (0) / Start (1)
DI2
Forward (0) / Reverse (1)
DI3
Constant frequency/speed selection
DI4
Constant frequency/speed selection
DI5
Ramp set 1 (0) / Ramp set 2 (1)
DI6
Not configured
RO1C
Ready run
RO1A
250 V AC / 30 V DC
2 A
RO1B
RO2C
Running
250 V AC / 30 V DC
RO2A
2 A
RO2B
RO3C
Fault (-1)
250 V AC / 30 V DC
RO3A
2 A
RO3B
B+
Embedded Modbus RTU (EIA-485)
A-
DGND
TERM
Serial data link termination switch
BIAS
Serial data link bias resistors switch
OUT1
Safe torque off. Factory connection. Both circuits
OUT2
must be closed for the drive to start. See chapter
The Safe torque off function in ACS580-01 (0.75
SGND
to 250 kW, 1.0 to 350 hp) hardware manual
IN1
(3AXD50000044794 [English]).
IN2

Advertisement

Table of Contents
loading