96 Maintenance
Replacing the AC fuses
WARNING! Only qualified electricians are allowed to do this work. Read the
complete safety instructions of the converter. If you ignore the instructions,
physical injury, death, or damage to the equipment can occur.
1. Disconnect the converter from the all power sources and make sure it is safe to start
the work. See the safety instructions.
2. Remove the shrouds in front of the fuses.
3. Open the M10 screws and remove the fuses.
4. Insert new fuses.
5. Re-assemble the parts in reverse order. The tightening torque for the M10 screws is
42 N·m (31 lbf·ft).
This figure is shown as an example.
2
3