COMPONENT IDENTIFICATION

FRONT VIEW

MS Indicator LED
NS Indicator LED
Configuration Jack
RJ-45 Modular Jack
1
4
2
5
3
6
■ INDICATORS
The following table defines the LED states of the MS, and
NS indicators.
ID
STATE
TO INDICATE
Green
Operating in a normal condition
Blinking Green
Standby (needs commissioning)
MS
Red
Critical failure
Blinking Red
Minor failure
OFF
No power supplied
Green
Link on-line and connections in the
established state
Blinking Green
Link on-line but no connections in
the established state
NS
Red
Critical link failure
Blinking Red
Minor link failure
OFF
No power supplied
• Ethernet Indicators
LINK: Turns on when the link is established
TX/RX: Turns on during transmitting or receiving data
■ SIDE DIP SW
(*) Factory setting
• Data Allocation: SW1, SW2
Data Allocation Type* must be assigned to each I/O module
position to specify how many data areas (four types) are to
be occupied by each.
Two bits from SW1 and SW2 are assigned to each posi-
tion, and data areas can be specified from the module No. 1
through 8. Setting for No. 9 and later modules is identical
to No. 8.
SW ASSIGNMENT
SW1-1
SW1-2
SW1-3
SW1-4
SW1-5
SW1-6
SW1-7
SW1-8
SW2-1
SW2-2
SW2-3
SW2-4
SW2-5
SW2-6
SW2-7
SW2-8
SW SETTING
OFF
OFF
ON
OFF
OFF
ON
ON
ON
* Refer to the specifications of the related series for the Data
Allocation Type of I/O modules.
Ethernet Indicator
LINK
TX/RX
MODULE NO.
1
2
3
4
5
6
7
8
DATA ALLOCATION
1
4
8
16
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp

SIDE VIEW

• Dual Communication: SW3-1
When two network modules are mounted, one must be
'Main' (OFF) network and the other must be 'Sub' (ON)
network. For single communication, the network module
must always be set to 'Main' (OFF).
DUAL COMMUNICATION
SW
MAIN (*)
SW3-1
OFF
• Input Error Data: SW3-2
Hold: When the communication from an input module is lost
due to the input module error, the network module holds the
signal and stands by until the communication recovers.
Set to '0': When the communication from an input module
is lost due to the input module error, the network module
outputs '0.'
INPUT ERROR DATA
SW
HOLD (*)
SW3-2
OFF
• I/O Data Area: SW3-3, 3-4
INPUT AREA
OUTPUT AREA
(Word)
(Word)
35
35
67
67
131
131
252
252
R3-NEIP1
Functions
SW3
SW2
SW1
4
8
8
3
7
7
2
6
6
1
5
5
4
4
ON
3
3
2
2
1
1
ON
ON
SUB
ON
SET '0'
ON
SW3-3
SW3-4
OFF (*)
OFF (*)
ON
OFF
OFF
ON
ON
ON
EM-8466 Rev.5 P. 2 / 7