INSTRUCTION MANUAL
CC-Link INTERFACE MODULE
(CC-Link Ver.1.10; for 32-point analog signals)
BEFORE USE ....
Thank you for choosing M-System. Before use, please check
contents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact M-System's Sales Office or representatives.
■ PACKAGE INCLUDES:
Network interface module ............................................ (1)
Terminating resistor (110Ω, 0.25W) ............................ (1)
■ MODEL NO.
Confirm Model No. marking on the product to be exactly
what you ordered.
■ INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.
POINTS OF CAUTION
■ CONFORMITY WITH EC DIRECTIVES
• The equipment must be mounted inside the instrument
panel of a metal enclosure.
• The actual installation environments such as panel con-
figurations, connected devices and connected wires may
affect the protection level of this unit when it is integrated
in a panel system. The user may have to review the CE
requirements in regard to the whole system and employ
additional protective measures to ensure CE conformity.
■ POWER INPUT RATINGS
Operational range & power consumption: Check the power
rating for the unit on the specification label.
Rating 100 – 120V AC: 85 – 132V, 47 – 66 Hz, approx. 20VA
Rating 200 – 240V AC: 170 – 264V, 47 – 66 Hz, approx. 20VA
Rating 24V DC: 24V ±10%, approx. 12W
■ UNPLUGGING THE MODULE
Before you remove the module from its base or mount it,
turn off the power supply for safety.
■ ENVIRONMENT
• Indoor use
• When heavy dust or metal particles are present in the air,
install the unit inside proper housing with sufficient ven-
tilation.
• Do not install the unit where it is subjected to continuous
vibration. Do not subject the unit to physical impact.
• Environmental temperature must be within -10 to +55°C
(14 to 131°F) with relative humidity within 30 to 90% RH
in order to ensure adequate life span and operation.
■ WIRING
• Do not install cables (power supply, input and output)
close to noise sources (relay drive cable, high frequency
line, etc.).
• Do not bind these cables together with those in which
noises are present. Do not install them in the same duct.
MODEL
■ AND ....
The unit is designed to function as soon as power is sup-
plied, however, a warm up for 10 minutes is required for sat-
isfying complete performance described in the data sheet.
INSTALLATION
Use the Installation Base Model R3-BSx, or Model R3-
BSWx for free I/O address capability.
Before mounting the Network Interface Module onto the
Base, be sure to configure the module as explained below.
■ DATA ALLOCATION
The setting determines the data area size assigned to each
I/O module mounted on the base.
The data sent/received via CC-Link is mapped according to
this setting.
See "COMPONENT IDENTIFICATION".
■ NODE ADDRESS & BAUD RATE
See "COMPONENT IDENTIFICATION".
■ NETWORK SLOTS ON THE BASE
I/O 1
I/O 2
With Model R3-BSx base, mount the I/O Modules from the
left end (I/O 1) to the right in order that the Network Mod-
ule assigns data areas from I/O 1.
Network Module(s) and Power Module are mounted basi-
cally at the right end though technically they could be
mounted in any position.
With Model R3-BSWx base, there is no limitation in mount-
ing positions as I/O address can be assigned freely to each
module using rotary switches equipped on the base.
R3-NC2
R3-NC2
I/O n
EM-842 Rev.8
P.  / 7

Advertisement

loading

Summary of Contents for M-system R3-NC2

  • Page 1 The unit is designed to function as soon as power is sup- plied, however, a warm up for 10 minutes is required for sat- Thank you for choosing M-System. Before use, please check isfying complete performance described in the data sheet.
  • Page 2: Component Identification

    R3-NC2 COMPONENT IDENTIFICATION ■ FRONT VIEW ■ SIDE VIEW Node Address Rotary SW RUN LED B RATE Baud Rate Rotary SW ERR LED Functions Configuration Jack Terminal Block ■ BAUD RATE ROTARY SW SW POSITION BAUD RATE 156 kbps 625 kbps 2.5 Mbps...
  • Page 3: Terminal Connections

    R3-NC2 TERMINAL CONNECTIONS Connect the unit as in the diagram below. ■ DIMENSIONS mm (inch) 27.5 (1.08) 109 (4.29) POSITIONING GUIDE 6–M3 SCREW TERMINAL COVER ■ CONNECTION DIAGRAM WIRING INSTRUCTIONS ■ SOLDERLESS TERMINAL mm (inch) INTERNAL Refer to the drawing below for recommended ring tongue COMM.
  • Page 4 Module 6 Module 7 Module 7 Module 8 Module 8 Unused Unused Thirty-two (32) data areas are available to the R3-NC2. Total data areas occupied by I/O modules must be within this limi- tation. EM-842 Rev.8 P. 4 / 7...
  • Page 5 R3-NC2 F E D C B A 9 8 7 6 5 4 3 2 1 F E D C B A 9 8 7 6 5 4 3 2 1 RX(n+0) Module Status RX(n+8) RX(n+1) Error Status (Burnout Bit)
  • Page 6 R3-NC2 I/O DATA DESCRIPTIONS ■ MODULE STATUS, ERROR STATUS, DATA ERROR STATUS Shows each module’s availability and error status. Module 1 Module 2 Module 3 Module 16 ■ ANALOG DATA (models: R3-SV4, YV4, DS4, YS4 and US4) 16-bit binary data.
  • Page 7 M-System’s option, the repair, replacement or refund of the purchase price of any M-System product which is defective under the terms of this warranty. To submit a claim under this warranty, the purchaser must return, at its expense, the defective M-System product to the below address together with a copy of its original sales invoice.