COMPONENT IDENTIFICATION

■ SIDE VIEW
Terminating Resistor SW
■ STATUS INDICATOR LED
ID
COLOR
Turns on when the internal 5V is sup-
PWR
Green
plied normally.
Turns on when the refresh data is re-
RUN
Green
ceived normally.
■ STATION ADDRESS
The left switch determines the sixteenths place digit, while
the right switch does the ones place digit of the address.
The data allocation is 4.
• Full-duplex communication
Setting "n" with the rotary switches, the addresses are n,
n+2, n+4 and n+6. (Range: 01H to 39H)
• Half-duplex communication
Four (4) addresses are assigned from the one set with the
rotary switch. (Range: 01H to 3CH)
Station Address Setting (x1)
Station Address Setting (x16)
SEN TRONIC
■ FRONT VIEW
Station Address Setting Rotary SW
Status Indicator LED
PWR
RUN
4
5
1
FUNCTION
056 222 38 18
mailbox@sentronic.com
AG
1
2
3
4
5
6
7
8
X10
X1
STATION ADD.
6
7
10 11 12 13
2
3
1
2
3
4
Network, Power Supply
Terminals
■ OPERATING MODE
(*) Factory setting
• Burnout (SW1-2)
SW1-2
OFF
ON
• Thermocouple Type (SW1-3, 1-4, 1-5, 1-6)
SW1-3
SW1-4
SW1-5
OFF
OFF
OFF
ON
OFF
OFF
OFF
ON
OFF
ON
ON
OFF
OFF
OFF
ON
ON
OFF
ON
OFF
ON
ON
ON
ON
ON
OFF
OFF
OFF
ON
OFF
OFF
OFF
ON
OFF
ON
ON
OFF
OFF
OFF
ON
ON
ON
ON
• Transfer Rate (SW1-8)
SW1-8
OFF
ON
Note : Be sure to set unused SW1-1 and 1-7 to OFF.
■ TERMINATING RESISTOR
To use the terminating resistor, turn the switch ON, and
OFF to invalidate. (Factory setting OFF)
www.sentronic.com
R7HL-TS4
Operating Mode Setting DIP SW (SW1)
PC Configurator Jack
ON
CNFG.
14
15 16 17 18
5
6
7
8
9
Input Terminals
BURNOUT
Upscale (*)
Downscale
SW1-6 THERMOCOUPLE TYPE
OFF
K (CA) (*)
OFF
E (CRC)
OFF
J (IC)
OFF
T (CC)
OFF
B (RH)
OFF
R
OFF
S
OFF
C (WRe 5-26)
ON
N
ON
U
ON
L
ON
P (Platinel II)
ON
(PR)
ON
PC Configurator setting
TRANSFER RATE
12 Mbps (*)
6 Mbps
EM-7812-B Rev.5 P. 2 / 5