Download Print this page

Component Identification - M-system R8-SVT8 Instruction Manual

Dc voltage input module

Advertisement

COMPONENT IDENTIFICATION

■ FRONT VIEW
Status Indicator LED
RUN
Input Status Indicator LED
1
5
2
6
3
7
4
8
Internal Bus Connector
Input Connector
AI_V
1
16
■ INDICATOR LED
ID
OPERATION
Status
OFF
Green ON
Green Blinking
Red ON
Red Blinking
Input
OFF
Status
Red Blinking
■ INPUT CONNECTOR ASSIGNMENT
PIN No.
1
2
1
3
4
5
6
7
8
9
10
11
12
16
13
14
15
16
■ SIDE VIEW
FUNCTION
Stopping
Valid host communication
Reading/writing configuration
Setting error
Parameter error
Input data in the range
Input data out of range
ID
FUNCTION
Input 1 (+)
In1
Input 1 (–)
Input 2 (+)
In2
Input 2 (–)
Input 3 (+)
In3
Input 3 (–)
Input 4 (+)
In4
Input 4 (–)
Input 5 (+)
In5
Input 5 (–)
Input 6 (+)
In6
Input 6 (–)
Input 7 (+)
In7
Input 7 (–)
Input 8 (+)
In8
Input 8 (–)
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
Function Setting
DIP SW
SW1
SW2
8
7
6
5
4
3
2
1
On
■ MODULE ADDRESS: SW1
SW1-1 through 1-4 determine the tenth place digit, while
SW1-5 through 1-8 do the ones place digit of the module
address.
Address is selected between 0 to 28.
(Factory setting: 0)
MODULE ADDRESS
×10
×1
0
1
2
3
4
5
6
7
8
9
■ OPERATING MODE
(*) Factory setting
• Input Range: SW2-1, 2
Same setting for all channels. Use PC Configurator to set
independent ranges per channel.
INPUT RANGE
-10 - +10V DC (*)
0 - 10V DC
0 - 5V DC
1 - 5V DC
• Terminator DIP SW: SW2-6
TERMINATOR SW
Without (*)
With
• Configuration Mode: SW2-8
CONFIGURATION MODE
DIP switch setting (*)
PC Configurator and communication
Note: Be sure to set unused SW2-3 through 2-5 and 2-7 to
OFF.
R8-SVT8
SW1
1
2
3
4
5
6
7
8
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
OFF
ON
OFF
OFF
OFF
ON
ON
OFF
ON
OFF
OFF
OFF
ON
OFF
ON
OFF
ON
ON
OFF
OFF
ON
ON
ON
ON
OFF
OFF
OFF
ON
OFF
OFF
ON
SW2
1
2
OFF
OFF
ON
OFF
OFF
ON
ON
ON
SW2-6
OFF
ON
SW2-8
OFF
ON
EM-9668 P. 3 / 5

Advertisement