Component Identification - M-system R30TS4 Instruction Manual

Thermocouple input module (4 points, isolated)

Advertisement

COMPONENT IDENTIFICATION

FRONT VIEW
RUN LED
ERR LED
CJC Sensor (CJM x 4)
Input Terminal Block
Terminal Fixing Screw
BOTTOM VIEW
Base Fixing Screw
■ STATUS INDICATOR LED
ID
COLOR
FUNCTION
RUN
Green
ON while network module operates normally
OFF in network module error
ERR
Red
OFF when input circuit and internal bus operate normally
Blinks in 1 sec. cycles when burnout is detected or with input value error (becomes less than the lower
limit or exceeds the upper limit of usable range).
Blinks in 400 msec. cycles with input circuit error (AD converter response failure).
ON with internal bus error
■ TERMINAL ASSIGNMENTS
1
+IN1
11
+CJ1
2
COM1
12
NC
3
+IN2
13
+CJ2
4
COM2
14
NC
5
NC
15
NC
6
+IN3
16
+CJ3
7
COM3
17
NC
8
+IN4
18
+CJ4
9
COM4
19
NC
10
NC
20
NC
RUN
ERR
Terminal Cover
Lock Tab
NO.
ID
FUNCTION
1
+IN1
T/C 1
2
COM1
Common 1
3
+IN2
T/C 2
4
COM2
Common 2
5
NC
No connection
6
+IN3
T/C 3
7
COM3
Common 3
8
+IN4
T/C 4
9
COM4
Common 4
10
NC
No connection
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
SIDE VIEW
NO.
ID
FUNCTION
11
+CJ1
CJC 1
12
NC
No connection
13
+CJ2
CJC 2
14
NC
No connection
15
NC
No connection
16
+CJ3
CJC 3
17
NC
No connection
18
+CJ4
CJC 4
19
NC
No connection
20
NC
No connection
R30TS4
Positioning Guide
Specifications
EM-9002 Rev.2 P. 2 / 5

Advertisement

loading