Parameter List - Salus ST100ZB Manual

Connected wireless system, module 5 – connected fan coil controls
Table of Contents

Advertisement

Appendix A
To change parameters, press and hold the
Use the
P
Name
P00
Type of thermostat
P01
Fan Coil Type
P02
Heat/Cool Option
P03
Valve Type
P04
Max . heating setpoint 41 to 92°F (5 to 33 .5°C)
P05
Min . heating setpoint 41 to 92°F (5 to 33 .5°C)
P06
Max . cooling setpoint 44 to 95°F (6 .5 to 35°C)
P07
Min . cooling setpoint
Protection heating
P08
setpoint
Protection cooling
P09
setpoint
Offset of internal
P10
sensor
Module 5 – Connected Fan Coil Controls

Parameter List

and
keys to scroll to "49" and press SELECT .
Values
0 = Non-Programmable
1 = Programmable
0 = 2 Pipe
1 = 4 pipe
For 2 Pipe
0=Heat Only
1=Cool Only
2 = Heat or Cool Manual changeover
3 = Heat or Cool Seasonal changeover
4 = Heat or Cool with Auxiliary Heat
For 4 Pipe:
2 = Heat or Cool Manual changeover
3 = Heat, Cool or Auto changeover
4 = Auto changeover only
0 = Normally Closed Valve
1 = Normally Open Valve
44 to 95°F (6 .5 to 35°C)
OFF or 41 to 92°F
(OFF or 5 to 33 .5°C)
OFF or 44 to 95°F
(OFF or 6 .5 to 35°C)
±6°F - 1°F increments
(±3°C - 0 .5°C increments)
MODE,
,
keys simultaneously .
Default
0
1
3
0
92°F
(33 .5°C)
41°F
(5°C)
95°F
(35°C)
44°F
(6 .5°C)
41°F
(5°C)
OFF
0°F
(0°C)
Description/Comment
Option #3 & #4 in the 2 pipe
configuration require the pipe
sensor (sold separately) to be
connected
Not displayed if P02 = 1
P05 < P04
P04 ≤ P06-1 .5°C
Not displayed if P02 = 1
P05 < P04
P05 ≤ P07-1 .5°C
Not displayed if P02 = 0
P07 < P06
P06 ≥ P04+1 .5°C
Not displayed if P02=0
P07 < P06
P07 ≥ P05+1 .5°C
If not OFF, P05 < P08 < P04
P08 < P09
If not OFF, P07 < P09 < P06
P08 < P09
A-1