Away Mode - Salus ST100ZB Manual

Connected wireless system, module 5 – connected fan coil controls
Table of Contents

Advertisement

Section 8

AWAY Mode

Fan Coil Thermostat terminals Ts and Tc are used to initiate or terminate an Away state in the device . The
Ts/Tc contact closure is configured by P16 as a Normally Open or Normally Closed contact, or as an input
to be ignored .
P16
0 (Disabled)
1 (Normally Closed)
2 (Normally Open)
A contact state change detected between the two terminals will initiate the Away timers (P19 or P20)
and once the timers expire, the device will enter or exit AWAY mode (indicated by the "person in
doorway" icon) . The timers are canceled if the contact input changes while the timers are active .
If Setback is selected when in AWAY mode (P21), the Setback set points (P17 and P18) will be in effect
(indicated by "leaf" icon), overriding any schedules .
Module 5 – Connected Fan Coil Controls
Operation
Ts/Tc
Status
0 (Setback Mode)
Ignored
Inactive
Open
Setback
Close
Inactive
Open
Inactive
Close
Setback
P21
1(Off Mode)
Inactive
Off
Inactive
Inactive
Off
8-5