Salus ST100ZB Manual page 40

Connected wireless system, module 5 – connected fan coil controls
Table of Contents

Advertisement

Appendix A
P
Name
Offset of external
P11
sensor
P12
External sensor
P13
Pipe sensor
Pipe sensor threshold
P14
for cooling
Pipe sensor threshold
P15
for heating
P16
Setback input
Setback heating
P17
setpoint
Setback cooling
P18
setpoint
Setback Unoccupied
P19
to Occupied delay
Setback Unoccupied
P20
to Occupied delay
Setback mode or Off
P21
mode when unoccu-
pied
P22
Accessory function
P23
TPI or Span
Modulation Response
P24
Time
P25
TPI heat control CPH
P26
TPI cool control CPH
CPH for Auxiliary
P27
Electrical Heater
Set span for heating
P28
using span control
Module 5 – Connected Fan Coil Controls
Parameter List
Values
±6°F - 1°F increments
(±3°C - 0 .5°C increments
0 = External sensor
1 = Zigbee remote sensor
0 = Analog input
1 = Normally open, default mode is Heat
2 = Normally open, default mode is Cool
3 = Normally closed, default mode is Heat
4 = Normally closed, default mode is Cool
50 to 77°F increment 1°F
(10 to 25°C increment 0 .5°C)
81 to 95°F increment 1°F
(27 to 35°C increment 0 .5°C)
0 = Disable
1 = Normally closed
2 = Normally open
50 to 68°F increment 1°F (10 to 20°C
increment 0 .5°C)
23 to 32°C increment 0 .5°C
(73 to 90°F increment 1°F)
1 to 3 seconds
2 to 30 minutes
0 = Setback mode
1 = Off mode
0 = No function
1 = Humidifier
2 = Dehumidifier
3 = ERV/HRV
0 = TPI
1 = Span control
0 = Slow response time
1= Fast response time
3 ~ 12 on/off cycle per hour
3 ~ 12 on/off cycle per hour
3 ~ 12 on/off cycle per hour
.5° to 2°F increment 0 .5°F
(0 .25° to 1°C increment 0 .25°)
Default
Description/Comment
0°F
(0°C)
Standalone mode: P12 = 0
0
Set
to EXT with
Displayed only if P01=0 and
P02=3 or 4 (2-pipe with sea-
sonal changeover or auxiliary
0
heat), which requires the pipe
sensor (sold separately) to be
connected .
50°F
(10°C)
86°F
(30°C)
0
15°C
Display only if P16=1/2
(59°F)
86°F
Display only if P16=1/2
(30°C)
1 sec
Display only if P16=1/2
2 mins
Display only if P16=1/2
1
Display only if P16=1/2
0
Normally Open
1
1
Display only if P23=0
6
Display only if P23=0
3
Display only if P23=0
6
Display only if P23=0
Display only if P23=1, device
0 .5°F
only display 0 .2/0 .5/0 .7/1 .0°C or
(0 .25°C)
0 .5/1 .0/1 .5/2 .0°F
key
A-2