Emerson Micro Motion CDM100M A Series Configuration And Use Manual page 212

Compact density meters
Table of Contents

Advertisement

Using ProLink III with the transmitter
5.
6.
7.
8.
9.
10.
11.
204
Figure C-7:
Connection over multidrop network
C
A. RS‐232 to Bell 202 converter
Ω resistance
B. 250–600
C. Devices on the network
D. Master device
Start ProLink III.
Choose Connect to Physical Device.
Set Protocol to HART Bell 202.
Tip
HART/Bell 202 connections use standard connection parameters. You do not need to
configure them here.
If you are using a USB signal converter, enable Toggle RTS.
Set Address/Tag to the HART polling address configured in the transmitter.
Tips
If this is the first time you are connecting to the transmitter, use the default address: 0.
If you are not in a HART multidrop environment, the HART polling address is typically left
at the default value.
If you are unsure of the transmitter's address, click Poll. The program will search the
network and return a list of the transmitters that it detects.
Set the PC Port value to the PC COM port that you are using for this connection.
Set Master as appropriate.
Option
Description
Secondary Use this setting if a primary HART host such as a DCS is on the network.
Primary
Use this setting if no other primary host is on the network. The
Field Communicator is a secondary host.