Electrical Requirements; Nominal Voltage Level; Power Quality; Electrical Requirements - Ja 100 External Air Compressor - Stratasys Fortus 360mc Site Preparation Manual

Hide thumbs Also See for Fortus 360mc:
Table of Contents

Advertisement

ELECTRICAL REQUIREMENTS

NOMINAL VOLTAGE LEVEL

The Nominal AC Line Voltage requirements for your system are 3-Phase 230 VAC ± 5%, phase balance ± 3%,
and a 20 Amp circuit. Operation of your system outside this range, even for short periods, is not recommended,
as it will result in degraded system performance and component life expectancy. The ideal output voltage from
the transformer is 230 VAC to 235 VAC.
Stratasys Part Number
600-00100
600-00200
600-00400

POWER QUALITY

AC power quality is key to reliable performance. The 360mc/400mc system is a precision tool that requires good
power quality. Its design incorporates a number of power quality control measures. Customers are required to
meet the power quality and nominal voltage requirements.
AC power should be provided to the system with a dedicated 3-phase feed. Recommendations of power quality
are given in IEEE Standard 141-1976 and FIPS PUB 94. Customers which are unsure of their power quality
need to contact their provider.

ELECTRICAL REQUIREMENTS - JA 100 EXTERNAL AIR COMPRESSOR

The optional external air compressor requires dedicated 50/60HZ, 230 VAC, Single Phase, 15 Amp, electrical
service. The air compressor includes an 8 ft. (2.5m) power cable requiring the installation of an AC service
connector.
Voltage
230VAC
230VAC
TRANSFORMER - JA 100 EXTERNAL AIR COMPRESSOR (NORTH AMERICA
ONLY)
A proven transformer solution for use with the JA-100 External Air Compressor.
Manufacturer
Federal Pacific
Manufacturer
Badger Magnetics
Badger Magnetics
Badger Magnetics
Frequency
Max Current
50Hz
6.8 Amps
60Hz
8.2 Amps
Part Number
Description
SB16N.250F
General purpose transformer, single
phase, 600 volt class, 60 Hz.
Transformer is wall mounted and is
light gray in color.
Incoming Service Voltage
200/208/220/240V WYE, 3 phase
380/400/415/440V WYE, 3 phase
480V WYE, 3 phase
Contact
Midwest Machine Tool Supply
1.800.327.9523
6

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fortus 400mc

Table of Contents