12. Serial output

The IEV valve driver has an RS485 or TTL serial output (only 1 of the 2 outputs can be used) for the
following possible uses:
connection to a Personal computer: the configuration parameters of the driver can be
programmed via Wizmate Prog Tool kit
XWEB system connection to supervise the operation of the valve driver
connection to a third party supervision system; the valve driver has Modbus RTU protocol
inside, with which the operating data can be read

13. Maximum power allowed

The IEV valve driver can control different types of motorised valves. The following table shows the
maximum current values that the windings of the valves can absorb.
Select the transformer that is suitable for the application on the basis of that shown in the table. The
type of Dixell transformer to use is indicated for every operating mode.
Do not disconnect or connect a valve to the IEV driver when it is connected to the power supply;
the connection or disconnection of the valve must always be done when the IEV driver is not
connected to power supply (IEV driver can be damaged).
NOTE:
Carefully read the technical manual supplied by the manufacturer of the valve body before using
the driver in order to prevent changing the data provided by the manufacturers of the valves,
and verify that the required currents are lower than those shown in the table below in order to
prevent damaging the control module.
DRIVE MODE
BIPOLAR Valves
UNIPOLAR valves
1592026260 IEV22-24D GB r.1.0 21.02.2019
Current 0.9A max
(4 wires)
Current 0.33A max
(5-6 wires)
CONFIGURATION
ONE VALVE
Entire step
→ TF20D
→ TF20D
IEV
TWO VALVES
Entire step
Current 0.9A max
per valve
→ TF40D
Current 0.33A max
per valve
→ TF20D
52/60