Number of return steps in opening mode after
Ec 12
the valve has been closed completely. These
decompress any closing spring inside the valve
or to prevent sealing the circuit.
For unipolar valves refer to the notes included
in paragraph 7.3.
Maximum number of adjusting steps of the
Ec 13
valve 1
(this value is set automatically by the controller
if EC9> 0).
For unipolar valves refer to the notes included
in paragraph 7.3.
Minimum number of adjusting steps of the
Ec 14
valve 1
(this value is set automatically by the controller
if EC9> 0).
For unipolar valves refer to the notes included
in paragraph 7.3.
Maximum current value per phase of the
Ec 15
stepper motor
(this value is set automatically by the controller
if EC9> 0)
Current stand-by value
Ec 16
(this value is set automatically by the controller
if EC9> 0)
Maximum number of steps per second of the
Ec 17
valve.
For unipolar valves refer to the notes included
in paragraph 7.3.
Selection of the bipolar valve body connected
Ec 18
to the driver (WARNING the unique and valid
reference has to be considered the
datasheet made by valve manufacturer)
0 = Custom
1 = Danfoss ETS – 25/50
2 = Danfoss ETS – 100
3 = Danfoss ETS – 250/400
4 = Alco EX4 – EX5 – EX6
5 = Alco EX7
6 = Alco EX8
7 = Configuration 1
8 = Configuration 2
Not used
Ec 19
1592026260 IEV22-24D GB r.1.0 21.02.2019
Valve 2 configuration
IEV
0
500
Full steps
Ec14 8000 Full steps
0
Ec13 Full steps
Ec16 100
mA
0
Ec15
mA
0
600
Full steps
0
8
x10 mA
x10 mA
39/60