CAPILLARY SENSOR THERMOSTAT T80F
GB
Operating Instructions and Installation
Description
• Capillary Sensor Thermostat with a visible external scale
• Easy to operate thanks to the large manual dial
• Temperature range 0 °C – 90 °C (tolerance 5 °C)
• Easy electrical connection thanks to the sufficiently large cable clamps

Installation

1. Thermostat to be mounted to the pipe's surface, attach to any place and secure the external sensor on the surface
of the system designated for the water transfer, where the temperature is supposed to be measured. Observe
the direct and safe contact with the surface. (Any insulation must be removed from the spot where the sensor
is going to be mounted)
2. The Capillary pipe located between the thermostat and the external sensor must not be curved (bent) in any case!

Electric Connection

1. Open the thermostat by pulling out the dial (1) and then release the large plastic screw (2).
2. Remove the lid from the case. Now you see the four plastic clamps, these must be connected in the follow-
ing way:
• Clamp C and 1 = opener
3. The thermostat will be opened as the temperature is increasing and will be closed as the temperature
decreases. (E. g. function = „Heating").
• Clamp C and 2 = opener
4. The thermostat will be closed as the temperature is increasing and will be opened as the temperature is
decreasing. (E. g. function = „Cooling").
• Clamp
= Grounding
The installation may be done by the professional heating technician only and in the accordance with the connection
plan. Moreover, the installation must comply the currently valid regulations and must comply as well as the specifica-
tions issued by your energy supplier. The installation must always be done when the electricity supply is switched off.
All the safety specifications must be observed.
Observe the maximum switching current stated in the technical specifications!

Technical Specifications

Operating Voltage:
Contact:
Switching Current:
Temperature Controlling Range: 0 °C – 90 °C
Sensor Unit:
Coverage:
230 V AC 50Hz, 400 V AC 50Hz
1 two-way contact
16 (4) A – 230 V, 6 (1) A – 400 V
liquid sensor
IP40
2