NGRM700 Intended use The NGRM700 is only intended for use in high-resistance grounded systems. In these systems, the NGRM700 monitors • the current through the neutral-grounding resistor (NGR), • the voltage between the star point of the transformer and earth (voltage drop across the NGR), •...
Page 4
W35…120AB W20…120 CTB31…41 Type W1-S35…W5-S210 Bender CT W... W...AB W...S... AN420 NGRM700: 50 mA NGRM700: 50 mA NGRM700: 5 A CT: Terminal k NGRM700: C NGRM700: C NGRM700: C CT: Terminal l AC/DC measuring current transformer connection (W…AB) 50 mm 1.97 in...
Page 5
NGRM700 Menu structure , Method, R NGR rel sense, rms rel rms rel, fund 1. Data meas. values fund rel fund fund rel, harm harm rel harm harm rel, L1L2 L2L3 , f, U L3L1 1-E rms 2-E rms 3-E rms 2.
Page 6
NGRM700 Recommended minimum value R (tripping level 50 %) Temperature range –40…+70 °C, field calibration at 25 °C (Values shown in brackets: Limited temperature range 0…+40 °C, field calibration at 25 °C) CD1000/CD1000-2 CD1000-2 CD5000 CD14400 CD25000 400 V 600 V...
Page 7
NGRM700 Language (8.2) Select RNGR nom (8.8) Date (8.3) CT primary (8.9) Time (8.4) CT secondary (8.10) Usys L-L (8.5) System voltage CT connection (8.11) 50 mA or 5 A Frequency (8.6) 50 or 60 Hz Field calibration (8.12) Start or do not start INGR nom (8.7)