Bender NGRM700 Quick Start Manual
Bender NGRM700 Quick Start Manual

Bender NGRM700 Quick Start Manual

Neutral grounding resistor monitor
Hide thumbs Also See for NGRM700:

Advertisement

Quick Links

Quickstart
NGRM700
EN
Neutral Grounding Resistor Monitor

Intended use

The NGRM700 is only intended for use in high-resistance earthed sys-
tems. In these systems, the NGRM700 monitors
the current through the NGR,
 
the voltage between the star point of the transformer and earth
 
(voltage drop across the NGR),
the condition of the neutral grounding resistor (NGR),
 
line-to-line and line-to-earth voltages.
 
This quick-start guide does not replace the operating manual of the device.
Download:
www.bender.de/manuals

Safety instructions

Risk of electrocution due to electric shock!
Touching live parts of the system carries the risk of:
 
DANGER
 
 
Before installing and connecting the device, make sure that the installation has
been de-energised. Observe the rules for working on electrical installations.
Removing FP200-NGRM
PH 1
Connection X1
I1
I2
I3
A
B
M+
Q2
Q1
+
NGRM700_D00292_02_Q_XXEN/06.2018
An electric shock
Damage to the electrical installation
Destruction of the device
1
X1
ET H
R
I1
Pulser IN
I2
Reset IN
I3
Test IN
A
Modbus RTU (A)
B
Modbus RTU (B)
Ground
M+
Analogue output
Q2
Open Collector: Pulser OUT
Q1
Open Collector: System health
+
Output for supply of external relays (+24 V, max. 100 mA)
X1
ET H
R
OFF
ON
RJ45:
Remote
max. 5 m
Switch
RJ45:
Ethernet
1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the NGRM700 and is the answer not in the manual?

Questions and answers

Summary of Contents for Bender NGRM700

  • Page 1: Intended Use

    Quickstart NGRM700 Neutral Grounding Resistor Monitor Intended use The NGRM700 is only intended for use in high-resistance earthed sys- tems. In these systems, the NGRM700 monitors the current through the NGR,   the voltage between the star point of the transformer and earth ...
  • Page 2 Dimension diagrams basic enclosure and FP200-NGRM Mounting position 55.50 2.19 61.40 2.42 63.35 2.49 0.12 0.236 223.50 8.80 4.92 5.91 8.07 8.31 9.06 9.65 66+0.5/-0 mm* 135.5 5.33 2.60+0.02/-0 in* 65.5 2.58 35.6 1.40 5.67 2.38 0.23 * IP 65: 68+0.7/-0 mm 2.68+0.03/-0 in NGRM700_D00292_02_Q_XXEN/06.2018...
  • Page 3 Trip fault fault 50mA 11 12 14 21 22 24 31 32 34 L2 L3 AC/DC 24...240 V * The PT ratio can be NGRM700 selected on the NGRM700 R s (G1) CD... FP200-NGRM E (G) Dig. IN/OUT Ethernet NGRM700_D00292_02_Q_XXEN/06.2018...
  • Page 4 40 m (6 mm²) Δn W35…120AB W20…120 CTB31…41 W1-S35…W5-S210 W...AB W... Type W...S... AN420 CT: k NGRM700: 50 mA NGRM700: 50 mA NGRM700: 5 A CT: l NGRM700: C NGRM700: C NGRM700: C CT installation W…AB 50 mm 1.97 in WXS... W...AB 250 mm 9.84 in...
  • Page 5: Menu Structure

    Menu structure , Method, R NGR rel sense, rms rel rms rel, fund 1. Data meas. values fund rel fund fund rel, harm harm rel harm harm rel, L1L2 L2L3 , f, U L3L1 1-E rms 2-E rms 3-E rms 2.
  • Page 6 Recommended minimum value (tripping level 50 %) Temperature range –40…+70 °C, field calibration at 25 °C (Limited temperature range 0…+40 °C, field calibration at 25 °C) CD1000/CD1000-2 CD1000-2 CD5000 CD14400 CD25000 400 V 600 V 690 V 1000 V 2400 V 4200 V 6000 V 6600 V 7200 V 11000 V 14400 V 25000 V 231 Ω...
  • Page 7: Initial Commissioning

    Initial commissioning The commissioning wizard (menu 8) queries the following parameters; additional settings: menu 6. Language (8.2) Select Date (8.3) Time (8.4) Usys L-L (8.5) System voltage Frequency (8.6) 50 or 60 Hz INGR nom (8.7) RNGR nom (8.8) CT primary (8.9) CT secondary (8.10) CT connection (8.11) 50 mA or 5 A...
  • Page 8: Initial Measurement

    3. > R 150 % 6. Buzzer Buzzer test © Bender GmbH & Co. KG Bender GmbH & Co. KG All rights reserved. Postfach 1161 • 35301 Gruenberg • Germany Reprinting only with permission Londorfer Str. 65 • 35305 Gruenberg • Germany of the publisher.

Table of Contents