Banner SureCross DX80N9X1S2N1M1 Manual page 4

Node with integrated battery
Table of Contents

Advertisement

Analog Configuration, Switch 2 OFF
Descriptions
Sample/Report Rate 15 minutes
Analog IN 2 (not available in integrated battery model), Discrete 1, and Discrete 2 are not powered from switched power terminals.
Discrete Configuration (Switch 2 ON)
The discrete configuration matches the switch power output (SP1) with the first discrete input (DI1). The analog inputs are disabled. The
discrete configuration is selected when switch 2 is in the ON position. Two sinking discrete outputs are active for this configuration.
Discrete Configuration, Switch 2 ON
Descriptions
Discrete Sinking (NPN)
Discrete Sourcing (PNP)
Booster 5V
Booster 10V
Warm-up Time 4 milliseconds
Warm-up Time 10 milliseconds
Sample/Report Rate 62.5 milliseconds
Sample/Report Rate 125 milliseconds
Sample/Report Rate 250 milliseconds
Sample/Report Rate 500 milliseconds
Sample/Report Rate 1 second
Sample/Report Rate 2 seconds
Host configured (override switches)
Sample/Report Rate 16 seconds
Discrete IN 1 uses switched power 1 (SP1). Analog inputs 1 and 2 are disabled.
Discrete Input Type
Select the type of discrete input sensors to use with this device: sourcing (PNP) sensors or sinking (NPN) sensors.
Modbus/User Configuration Tool (UCT) or DIP Switch Configured
In Modbus/UCT Configured mode, the device parameters are changed using the User Configuration Tool (UCT) or a Modbus command.
All DIP switch positions are ignored. In DIP Switch Configured mode, use the DIP switches to configure the parameters listed in the table.
Wiring Your SureCross® Device
Use the following wiring diagrams to first wire the sensors and then apply power to the SureCross devices.
Switch Power (with FlexPower)
Efficient power management technology enables some FlexPower devices to include an internal power supply, called switch power (SP),
that briefly steps up to power sensors requiring 5, 10, or 15V power (ideally, 4 to 20 mA loop-powered sensors). When the switch power
output cycles on, the voltage is boosted to the voltage needed to power the sensor for a specific warmup time. This warmup time denotes
how long the sensor must be powered before a reliable reading can be taken. After the warmup time has passed, the input reads the
sensor, then the switch power shuts off to prolong battery life. The switch power voltage, warm-up time, and sample interval are configu-
rable parameters.
• To reduce power consumption and extend battery life, slower sample and reporting rates are used. Faster sample and report rates
can be configured, but this will decrease the battery's life. For details, refer to the included table of DIP switch configurable parame-
ters.
• The FlexPower switched power management system can operate a FlexPower Node and a sensing device for up to five years on a
single lithium D cell.
4
3
4
3
4
OFF*
ON
OFF*
ON
www.bannerengineering.com - tel: 763-544-3164
SureCross DX80 Node with Integrated Battery
DIP Switches
5
6
7
ON
ON
DIP Switches
5
6
7
OFF*
ON
OFF
OFF
OFF
OFF
OFF
ON
OFF
ON
ON
OFF
ON
OFF
ON
ON
ON
ON
8
ON
8
OFF
ON
OFF
ON
OFF
ON
OFF
ON
P/N 147502 Rev. E