List Of Available Registers - LAUMAS TLU Installation And User Manual

Table of Contents

Advertisement

a time-out for reception of the answer. If it does not receive an answer it deduces that there has
been a communication error.
In the case of the string received correctly but not executable, the slave responds with an
EXCEPTIONAL RESPONSE. The "FUNCTION" field is transmitted with the MSB at 1.
EXCEPTIONAL RESPONSE
Address
Function
A
Funct + 0x80
CODE
1
ILLEGAL FUNCTION (The function is not valid or is not supported)
2
ILLEGAL DATA ADDRESS (The specified data address is not available)
3
ILLEGAL DATA VALUE (The data received has an invalid value)
The MODBUS-RTU protocol implemented on this instrument can manage a maximum of 32
registers read and written in a single query or response.
R = the register may only be read
W = the register may only be written
R/W = the register may be both read and written
H = high half of the DOUBLE WORD containing the number
L = low half of the DOUBLE WORD containing the number
REGISTER
DESCRIPTION
40001
Firmware Version
40002
Instrumento type
40003
Year of manufacture
40004
Serial Number
40005
Program type
40006
COMMAND REGISTER
40007
STATUS REGISTER
40008
GROSS WEIGHT H
40009
GROSS WEIGHT L
40010
NET WEIGHT H
40011
NET WEIGHT L
40012
PEAK WEIGHT H
40013
PEAK WEIGHT L
40014
Divisions and Units of measure
40015
Not used
40016
Not used
40017
SETPOINT 1 H
40018
SETPOINT 1 L
40019
SETPOINT 2 H
Code
2 byte
CRC
DESCRIPTION

LIST OF AVAILABLE REGISTERS

- 30 -
Saving in EEPROM
-
-
-
-
-
NO
-
-
-
-
-
-
-
-
Only after
command '99'
of the
ACCESS
R
R
R
R
R
R/W
R
R
R
R
R
R
R
R
R
R
R/W
R/W
R/W