Siemens 7XV5655-0BA00 Application Instructions page 49

Serial hub
Hide thumbs Also See for 7XV5655-0BA00:
Table of Contents

Advertisement

Mechanical tests, vibration and shock stress
- stationary use
Vibration
IEC 60255-21-1, Class 2
IEC 60068-2-6
Shock
IEC 60255-21-2, Class 1
Seismic vibration
IEC 60255-21-3, Class 1
IEC 60068-3-3
Mechanical tests, vibration and shock stress
- during transport
Vibration
IEC 60255-21-1, Class 2
IEC 60068-2-6
Shock
IEC 60255-21-2, Class 1
IEC 60068-2-27
Shock
IEC 60255-21-2, Class 1
IEC 60068-2-27
C limatic tests
1 3 B
Recommended operating temperature
Limit temp. during operation
Limit temp. during storage
Limit temp. during transport
Humidity
Maximum relative humidity
Installation altitude
Maximum height above sea level
All devices must be installed so that they are not exposed to direct sunlight, nor subject to great
fluctuations in temperature that may cause condensation.
SIEMENS AG
Sinusoidal, 10 to 58 Hz : 0.075 mm ampl.
58 to 150 Hz : 1.0 g accel.
20 cycles in 3 orthogonal axes
Semi-sinusoidal, 5 g accel., 11 ms duration
3 shocks each in both directions of the
3 axes
Sinusoidal, 1 to 8 Hz : 4 mm ampl.
horizontal
1 to 8 Hz : 2 mm ampl. vertical
8 to 35 Hz : 1 g accel., horizontal
8 to 35 Hz : 0.5 g accel., vertical
1 cycle in 3 orthogonal axes
Sinusoidal, 5 to 8 Hz : 7.5 mm ampl.
8 to 150 Hz : 2 g accel.,
20 cycles in 3 orthogonal axes
Semi-sinusoidal, 15 g accel., 11 ms duration
3 shocks each in both directions of the 3
axes
Semi-sinusoidal, 10 g accel., 16 ms duration
1000 shocks each in both directions of the
3 axes
0 °C to 55 °C
-5 °C to +70 °C
-25 °C to +55 °C (factory packing)
-25 °C to +70 °C (factory packing)
80 % at temperatures up to 31 °C,
decreasing linearly down to 50 % at 40 °C
2,000 m
Page 49 of 51
Manual 7XV5655-0BA00
C53000-G1176-C174-4