Manual 7XV5655-0BA00
F eatures
2 6 B
Protocol detection according to EN 60870-5-101/103 and DIGSI protocol (similar
to IEC60870-5-103), UDP protocol with error detection and correction
A 10-Mbit Ethernet interface (10BaseT) for the 10/100 Mbit network.
RS232/RS485 (switchable port) or FO interface for data transfer.
Serial baud-rate and data format to the terminal devices is automatically set by
the application, e.g. DIGSI 4 at 2400 Bd to 57.6 kBd (115.2 kBd) with data
formats 8N1, 8N2, 8E1.
Re-set to default values (factory settings) with INIT button: 9600 baud, 8N1
DIP switch for RS232/RS485 selection and RS485 bus termination as well as FO
idle state
Enhanced security is possible with password protection
LED displays for operating voltage and data traffic are located on the front panel.
DIN rail module in the plastic housing with integrated wide-range power supply
unit (24 - 250 V DC and 60 - 230 V AC) which provides connection to all
conventional substation batteries or AC power systems.
Protective conductor (PE) connection