Siemens 7XV5655-0BA00 Application Instructions page 47

Serial hub
Hide thumbs Also See for 7XV5655-0BA00:
Table of Contents

Advertisement

Standards:
Insulation tests
Standards:
Voltage test (100% test) all circuits except
auxiliary voltage and communication interfaces
Voltage test (100% test) on auxiliary voltage
Voltage test (100% test) only locked
communication interfaces
Surge withstand capability test
all circuits except communication interfaces,
class III
Warning
The 7XV5655-0BA00 is specifically intended for installation in a switchgear
cubicle or distribution housing. After installation protective covering must be
placed around the entire area of the terminals. Only then is the device
sufficiently protected against impermissible contact with live parts.
EMC tests for immunity (type tests)
Standards:
High Frequency Test
IEC 60255-22-1, Class III
and VDE 0435 Part 303, Class III
Electrostatic Discharge
IEC 60255-22-2, Class III
Irradiation with RF field , frequency sweep
IEC60255-22-3, Class III
IEC61000-4-3, Class III
SIEMENS AG
IEC 60255 (product standard)
IEEE Std C37.90.0/.1/
VDE 0435
For more standards, see each function
IEC 60255-5 and IEC 60870-2-1
2.5 kV (rms), 50 Hz
3.5 KV DC
500 V (rms), 50 Hz
(type test)
5 kV (peak value); 1.2 / 50 µs; 0.5 J;
3pos./neg. surges at 5s intervals
IEC 60255-6 and -22 (product standards)
EN61000-6-2 (generic standard)
VDE 0435 part 301DIN VDE 0435-110
2.5 KV (peak); 1 MHz;‫ 51 = ז‬ms; 400 surges
per s; test duration 2s; Ri = 200 Ω
8 KV contact discharge; 15 KV air discharge
pos./neg. polarity, 150 pF; Ri = 330 Ù
10 V/m, 80 MHz to 1000 MHz: 80% AM, 1
kHz
Page 47 of 51
Manual 7XV5655-0BA00
C53000-G1176-C174-4