Figure 2-3 Installation Altitude - Siemens MICROMASTER 430 Manual

Hide thumbs Also See for MICROMASTER 430:
Table of Contents

Advertisement

2 Installation
Humidity Range
Altitude
Shock and Vibration
Electromagnetic Radiation
Atmospheric Pollution
Water
Installation and cooling
22
www.eltra-trade.com
Relative air humidity ≤ 95 % Non-condensing
If the inverter is to be installed at an altitude > 1000 m or > 2000 m above sea
level, derating will be required:
Permissible output current
100
%
80
2000
0
1000
Installation altitude in m above sea level
Figure 2-3
Installation altitude
Do not drop the inverter or expose to sudden shock. Do not install the inverter in an
area where it is likely to be exposed to constant vibration.
Mechanical strength to DIN IEC 68-2-6
Ø Deflection:
0.075 mm (10 ... 58 Hz)
Ø Acceleration:
9.8 m/s
Do not install the inverter near sources of electromagnetic radiation.
Do not install the inverter in an environment, which contains atmospheric pollutants
such as dust, corrosive gases, etc.
Take care to site the inverter away from potential water hazards, e.g. do not install
the inverter beneath pipes that are subject to condensation. Avoid installing the
inverter where excessive humidity and condensation may occur.
CAUTION
The inverters MUST NOT be mounted horizontally.
The inverters can be mounted without any clearance at either side.
The following clearances above and below the inverter are necessary:
Ø FS C
100 m
Ø FS D, E
300 mm
Ø FS F
350 mm
When mounting one inverter above the other, the ambient operating temperature
must be adhered to. Make sure that the cooling vents in the inverter are positioned
correctly to allow free movement of air.
Permissible input voltage
100
%
80
77
0
1000
3000
4000
Installation altitude in m above sea level
2
(> 58 ... 500 Hz)
MICROMASTER 430
2000
3000
4000
Operating Instructions
6SE6400-5AC00-0BP0