Issue 05/02
3.2.2.1
Commissioning with the BOP-2
You can alter parameter values via the BOP-2. To set parameters on this panel,
NOTICE
♦
The BOP-2 motor control functions are disabled by default. To control the
motor via the BOP-2, parameter P0700 should be set to 1 and P1000 set to 1.
♦
The BOP-2 can be fitted to and removed from the inverter whilst power is
applied.
♦
If the BOP-2 has been set as the I/O control (P0700 = 1), the drive will stop if
the BOP-2 is removed.
Table 3-2
Parameter
P0100
P0307
P0310
P0311
P1082
ATTENTION
MICROMASTER 430 can only be operated using a BOP-2 bedient werden.
If a BOP or AOP is used, the following is shown on the display
MICROMASTER 430
Operating Instructions
6SE6400-5AE00-0BP0
you must remove the SDP and attach the BOP-2 (see
Appendix A).
The BOP-2 features a five-digit, seven-segment display
for showing parameter numbers and values, alarm and
fault messages and setpoints and actual values.
Parameter sets cannot be saved via the BOP-2.
Table 3-2 shows the factory default settings for operation
via the BOP-2.
Default settings for operation using the BOP-2
Meaning
Operating Mode Europe/US
Power (rated motor)
Motor frequency rating
Motor speed rating
Maximum Motor Frequency
Default Europe (North America)
50 Hz, kW (60 Hz, hp)
Dimension (kW (Hp)) depending on setting of P0100.
[Value depending on variant.]
50 Hz (60 Hz)
1395 (1680) rpm [depending on variant]
50 Hz (60 Hz)
3 Commissioning
.
39