J8 15V / 10V Jumper; J17 Analog Signal Input (Voltage Position); J17 Analog Signal Input (Current Position); J9 Enable / Inhibit Jumper - KB Electronics Penta Power KBRG-212D Installation And Operation Manual

Regenerative drive, variable speed scr control full wave 4-quadrant
Hide thumbs Also See for Penta Power KBRG-212D:
Table of Contents

Advertisement

7.5 J8 – Analog (Signal) Input Voltage –
The output of this control is normally controlled
with the main potentiometer. However, an
analog voltage (isolated) may also be used in
place of a potentiometer. The control can be
scaled for
appropriate position "15V" or "10V". The scaling
can be further adjusted with the SCALE Trimpot.
Refer to Section 6.9, (Signal Following) on page
17, and Figure 16, for additional information.
7.6 J17 – Analog Signal Input – J17 is used in
conjunction with jumper J8 and the Main
Speed Potentiometer for, the input of a voltage
or a voltage or current signal . Refer to Section
6.9, (Signal Following) on page 17 and Figures
17A and 17B.
FIGURE 17A - J17
ANALOG SIGNAL INPUT
"VOLTAGE POSITION (DEFAULT)"
J17
VOLT
7.7 J9 – Enable (EN) / Inhibit (INH) – The control
can be electronically stopped or started with the
inhibit circuit, depending upon the position of
Jumper, J9. The control can also be started and
stopped with the Enable (Factory Set) function.
(The enable circuit functions opposite to that of
the inhibit circuit). See Figure 18 and Section
6.10, on page 18, for wiring information.
22
0 – 10VDC by placing J8 in the
CUR
FIGURE 16 - J8 15V / 10V
JUMPER
(Shown in the 10V Position)
J8
15V
J8
15V
10V
(Shown in the 15V Position)
Default Position
FIGURE 17B - J17
ANALOG SIGNAL INPUT
"CURRENT POSITION"
J17
VOLT
CUR
FIGURE 18 - J9 ENABLE /
INHIBIT JUMPER
(Shown in the Enable Position)
INH
EN
J9
INH
J9
(Shown in the Inhibit Position)
10V
EN

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents