Electrical Connections; Terminal Block Wiring Information - KB Electronics Penta Power KBRG-212D Installation And Operation Manual

Regenerative drive, variable speed scr control full wave 4-quadrant
Hide thumbs Also See for Penta Power KBRG-212D:
Table of Contents

Advertisement

6

ELECTRICAL CONNECTIONS

WARNING! READ SAFETY WARNING, ON PAGE 5, BEFORE USING THIS
CONTROL.
CAUTION! To avoid erratic operation, do not bundle AC line and motor connections
with potentiometer connections, voltage following connections, Start/Stop switch
connections, inhibit connections, or any other signal connections. Use shielded
cables on all signal connections over 12" (30 cm) long. Shield should be earth
grounded on the control side only
Connect control in accordance with National Electric Code requirements and other local
codes that apply. The KBRG-212D does not contain AC line or armature fusing. It is
recommended that a 20 Amp fuse or circuit breaker be installed on each AC line
conductor not at ground potential. Connect control, in accordance with illustrations in this
section. A separate AC line switch or contactor must be connected as a disconnect switch
so that contacts open each ungrounded conductor. In addition, Table 6, details the
connection, wiring and torque information.
Terminal Block
Designation
TB1
TB2
TB3
6.1 AC Line Connection – Connect the AC line to L1 and L2 terminals of TB1 as
shown in Figure 3, on page 14.
Note: There are no AC Line or Armature fuses supplied with this control. See Section
6.3, on page 14.
6.2 Motor Armature – Connect motor armature to terminal Ml and M2. (Be sure
jumper J3 is set to match motor voltage. See Figure 3, on page 14 and Section
7.2, on page 20.
TABLE 6 – TERMINAL BLOCK WIRING INFORMATION
Connection
Designation
Power / Control
Connections
L1, L2, M1, M2
F+, F-
.
Supply Wire Gauge
(AWG – Copper)
Minimum
Maximum
22
18
22
Maximum
Tightening
Torque
(lbs- in)
14
12
14
3.5
3.5
3.5
13