The waste gas duct connection must conform with the conditions specified in the regulations
TSI and local gas distribution companies.

WALL HUNG BOILERS WITH FLUE DUCTS

The boiler must be connected to a duct before use. The duct of wall hung boiler must not be
connected to stairwells or windows. The duct of wall hung boiler must not be connected to
stairwells, opening areas for light or windows.
The waste gas pipe must be connected to the duct as shortly as possible. The
imperviousness at the connection points must be maintained.
The duct height must 4 meters.
While using single brackets, the horizontal length of duct pipe must be 2 meters.. While using
two brackets, the length of the duct pipe must be maximum 1 meter.
As for the wall hung boilers in the attic storeys the horizontal length must be 1meter max.
and single bracket must be used.
The diameter of duct pipe must be 130mm for 24kW devices, 140mm. for 28-32 kW devices.
Waste gas pipe must be connected to the duct with a little slope.
Caution: Duct channel must be cleaned once a year.
HERMET‹C WALL HUNG BOILERS
The flue kit provided with the device must be installed properly and you must ensure that it does not
leak. The Duct kit is composed of connection bracelet of two pipes having a 60/100mm diameter and
impervious materials. The waste gas discharge of hermetic wall hung boilers must be directed to
outside.
The waste gas system operating at inclined position should have a 3% downward slope.
CAUTION : The maximum allowed pipe length should be diminished by 1 meter at every
bracket insertion.
There are examples of duct kit connection shapes. In order for the device perform well, the
maximum dimensions given hereunder must be considered.
It is recommended that pipes longer than 8 meters should be isolated. (just at the parallel pipe
connection).