Work Flow - Omron CV/CVM1 Replacement Manual

From cv/cvm1 to cs1
Table of Contents

Advertisement

1.

Work flow

This section describes the flow of work you have to follow when you replace CV/CVM1 CPU Units with CS-series
CPU Units. Read the reference pages for details.
1) Preliminary Steps: Take the following steps before starting the replacement work.
Start
Selecting the model
Preparing Units
Reading PLC data
Converting and
modifying data
Continue actual replacement work
2) Actual replacement work flow: The following flow shows the procedure taken to replace the CV/CVM1 to CS.
Replacing Units
Wiring
Writing data to CS
Checking operation
Replacement
completion
2
Description
Select the corresponding CS-series Units, support software
and connecting cables to be used for replacing CV/CVM1
with CS. Some CV/CVM1 models can be used with CS, while
the others cannot. Read the reference pages to understand
recommended models and precautions and select a model.
Prepare the selected Units, support software and connecting
cables.
Load the program, I/O Memory and other settings from the
CV/CVM1 using the programming software and connecting
cable.
Convert the data read from CV/CVM1 for CS.
Most of the data can be automatically converted while some
instructions are not. It depends on the used instructions or
the Unit model. Refer to the reference pages and modify the
data and program manually.
Description
Replace the CV/CVM1 Units with the prepared CS Units.
* Refer to the SYSMAC CS Series Programmable Controllers
OPERATION MANUAL (Cat. No. W339) and User's manual
for Special I/O Units and CPU Bus Units for details about
installation.
Wire the installed Units.
* Refer to the SYSMAC CS Series Programmable Controllers
OPERATION MANUAL (Cat. No. W339) and User's manual
for Special I/O Units and CPU Bus Units for details about
installation.
Transfer the converted data from CV/CVM1 to CS. To see if
the wires are properly connected, operate inputs and outputs
and check the signals.
Turn on the power and check the operation.
1. If production is conducted between the time from when the data was read and when it was
written, the present value in the program could be changed. Upload the data right before the
replacement work, modify it (if necessary), and download it to the new PLC.
2. The cycle times of CV/CVM1 and of CS are different, which may affect system operation.
Adjust the cycle time from the PLC settings. Some system configuration requires additional
program. Add the program, if necessary.
Reference page s
2. Selecting the model
3. Reading data from
CV/CVM1
4. Converting and
changing the program for
CS
Reference page
Related manuals
5. Writing the data to CS