Follow the below work flow to replace C200HX/HG/HE with CJ2. Refer to the reference pages for details.
1.

Work flow

1) Preliminary Steps: Take the following steps before starting the replacement work.
Start
Selecting the model
Preparing Units
Reading PLC data
Converting and modifying data
Continue to actual replacement work
2) Actual replacement work: Take the following steps to replace C200HX/HG/HE with CJ2.
Replacing Units
Wiring
Writing the data to CJ2
Checking operation
Replacement completion
2
Description
Select the units, programming software, and connecting
cables to replace C200HX/HG/HE with CJ2.
The C200H-series Units cannot be used with CJ2. Read the
reference pages (recommended models and remarks) and
select the models.
Prepare the units, programming software, and connecting
cables.
Load the program, I/O Memory and other settings from the
C200HX/HG/HE using the programming software and
connecting cable.
Convert the data read from C200HX/HG/HE for CJ2.
Most of the data can be automatically converted; however, some
instructions and some Unit data cannot be converted.
Refer to the reference pages and modify the data and program
separately.
Description
Install the prepared Units instead of C200H-series Units.
*Refer to the SYSMAC CJ Series CJ2 CPU Unit Hardware
USER'S MANUAL (Cat. No. W472) and user's manuals for
Special I/O Units and CPU Bus Units for details of installation.
Wiring for the installed Units.
*Refer to the SYSMAC CJ Series CJ2 CPU Unit Hardware
USER'S MANUAL (Cat. No. W472) and user's manuals for
Special I/O Units and CPU Bus Units for details of wiring.
Transfer the converted data to CJ2
To check the wiring, operate input and output bits to see if
they operate correctly.
Turn ON the power and check the operation.
1.
If production is conducted between uploading the program and executing replacement
work, data handled by the program may change. If so, upload the data right before the
replacement work, modify data (if necessary), and download it to the new PLC.
2.
The cycle time of C200HX/HG/HE and CJ2 are different, which may affect system
operation. If so, it is necessary to adjust cycle time in the PLC Setup.