5.

Specifications

Table 1, Line Mode Specifications
MODEL
Input Voltage Waveform
Nominal Input Voltage
Low Loss Voltage
Low Loss Return Voltage
High Loss Voltage
High Loss Return Voltage
Max AC Input Voltage
Nominal Input Frequency
Low Loss Frequency
Low Loss Return Frequency
High Loss Frequency
High Loss Return Frequency
Output Short Circuit Protection
Efficiency (Line Mode)
Transfer Time
Output power derating:
When AC input voltage drops to 95V or
170V depending on models, the output
power will be derated.
CPS3000ECH48A
CPS5000ECH48A
CPS5000ECH48A-P
Sinusoidal (utility or generator)
230Vac
170Vac±7V (UPS)
90Vac±7V (Appliances)
180Vac±7V (UPS);
100Vac±7V (Appliances)
280Vac±7V
270Vac±7V
300Vac
50Hz / 60Hz (Auto detection)
40±1Hz
42±1Hz
65±1Hz
63±1Hz
Line mode: Circuit Breaker
Battery mode: Electronic Circuits
>95% ( Rated R load, battery full charged )
10ms typical (UPS); 20ms
typical (Appliances)
Output Power
Rated Power
20% Power
90V
170V
34
280V
Input Voltage