DC Power and
Grounding
Requirements
iPlex Installation and Hardware Specification Guide
ATTENTION!
It is important to maintain proper air circulation through the iPlex
chassis. Failure to maintain proper air flow and adequate air space
can cause the iPlex to overheat and fail. Since the iPlex airflow is
from side-to-side it is recommended that you maintain a minimum 6-
inch (15 cm) clearance on both sides between the chassis air intake
and air exhaust on the sides and a cabinet wall or other barrier. You
should also calculate the heat load from other heat generating
devices and determine if an off-set is required between units to mini-
mize the effects of heat exhaust. Always allow a minimum separation
between the hot air exhaust on one chassis and the air intake on
another chassis.
STA TUS
ACT IVE
POW ER
LINK ACT
SCM
IVE
ONL INE
ETH 1
ALA RM
MCM
GE 1
ETH 2
MAJ OR
GE 2
MINO R
The chassis has only one power terminal with no redundant connection points for
two CO power sources.
WARNING:
DANGER!
Install a protective earth (PE) or ground connection before
connecting power supply and telecommunication lines, using wire
gauge in accordance with this document and local codes.
Use a power source that provides current overload protection and is
rated as indicated in this document.