Huawei FusionModule 1000A40 Maintenance Manual page 162

Hide thumbs Also See for FusionModule 1000A40:
Table of Contents

Advertisement

FusionModule1000A40 IT Solution
Maintenance Guide (2016.05, AI Version)
Materials: spare smoke detector
Document: fire extinguishing device layout diagram (CE)
Skill requirement: fire engineer
Procedure
Step 1 Disconnect the battery cables, and switch off the input circuit breaker of the extinguishant
control panel.
Step 2 Hold the smoke detector, and rotate it counterclockwise to remove it from the base.
Figure 5-82 Removing a smoke sensor
Step 3 Remove cables from the base using a Phillips screwdriver.
Step 4 Remove the screws on the base using a Phillips screwdriver, and remove the base.
Step 5 Install the new base to the same position, and reconnect the cables.
Step 6 Insert the new smoke detector into the base, and rotate it clockwise until it locks in.
Step 7 Switch on the input circuit breaker of the extinguishant control panel, and connect the cables
to the battery.
Issue 04 (2018-01-05)
For the diagrams, see the initial configuration parameter manual for the solution in use.
Before replacing the smoke detector, inform the related administration department of the
temporary downtime of the fire control system. After the replacement, inform the
administration department that the system has become operational.
As a terminal resistor is connected to the last smoke detector in the loop in parallel, remove the terminal
resistor from the faulty smoke detector, and connect the resistor to the new smoke detector when you
replace the smoke detector.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
5 Components Replacement
154