Huawei FusionModule 1000A40 Maintenance Manual page 111

Hide thumbs Also See for FusionModule 1000A40:
Table of Contents

Advertisement

FusionModule1000A40 IT Solution
Maintenance Guide (2016.05, AI Version)
1.
2.
3.
4.
Figure 5-28 Removing the emergency door release button
Step 2 Install a new emergency door release button.
1.
2.
3.
4.
Figure 5-29 Installing the emergency door release button
Step 3 Check that the new emergency door release button is working properly.
Remove the cover of the emergency door release button using a screwdriver, press the button, and rotate
the door handle clockwise to open the pre-fab. module door. If the door can be opened, the emergency
door release button is working properly.
----End
Issue 04 (2018-01-05)
Remove screws securing the emergency door release button, as shown by (1) in
5-28.
Remove the glass panel of the emergency door release button, as shown by (2) and (3) in
Figure
5-28.
Remove screws securing the base, as shown by (4) in
Disconnect cables and remove the emergency door release button.
Connect cables.
Tighten screws on the base, as shown by (1) in
Install the glass panel, as shown by (2) and (3) in
Tighten screws, as shown by (4) in
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Figure
Figure
5-29.
Figure
5-29.
Figure
5-29.
5 Components Replacement
Figure
5-28.
103