Figure 5-60 Removing the battery fixing plate
Step 4 Remove the cables from the battery, and take out the battery.
Step 5 Remove all cables connected to the fire alarm control panel terminals, and move the
corrugated pipes and cables outside of the box.
Keep labels on the cables intact so that cables can be connected to the correct terminals later.
Step 6 Remove the screws using a Phillips screwdriver, and take out the faulty fire alarm control
panel.
Step 7 Install the new fire alarm control panel in the same position.
Step 8 Put the corrugated pipes and cables back to the box, and reconnect the cables according to
labels.
Step 9 Install the battery in the same position, and connect cables in the same way.
Figure 5-61 Connecting battery cables
Step 10 Use a Phillips screwdriver to secure the battery fixing plate.