3.2 Monthly Maintenance

3.2.1 Power Supply and Distribution System

Table 3-2 Monthly maintenance checklist for the power supply and distribution system
Item
Luminance
of the
three-phase
indicators
SPD
indicator
and SPD
circuit
breaker
status
Buttons on
the PD510
electricity
meter panel
Issue 04 (2018-01-05)
Item
Method
Access
Check the door
controller
status list in the
communic
management
ation
system.
status
Method
Check the
luminance of the
three-phase
indicators.
Check the SPD
indicator and SPD
circuit breaker
status.
Push any button on
the PD510
electricity meter
panel.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Expected
Result
The coverage of
the camera is
optimal.
All door status
icons under the
access controller
blink.
Expected
Troubleshooting
Result
The
Replace an indicator if it generates
three-phase
no or dim light.
power
indicators are
steady on.
The SPD
If an SPD indicator is red, replace
indicator is
the SPD in a PDC..
green.
The SPD
If an SPD circuit breaker is
circuit breaker
switched to OFF, switch it to ON.
is switched on.
1. If the LCD does not display
The PD510
information properly (no display
electricity
or fuzzy), check whether the
meter LCD
power cable is properly
lights up and
connected.
displays
information
2. If the power cable is correctly
properly.
connected, Replace the PD510
electricity meter.
3 Maintenance
Troubleshooting
If the area covered by the
camera is inappropriate,
adjust the camera coverage
by following the instructions
in documents delivered with
the camera.
If a door status icon is
dimmed (unavailable), check
the access controller and
network status.