FusionDC1000A Prefabricated All-in-One Data
Center
Quick Guide (2020, Nigeria, River)
Issue
01
Date
2020-11-30
HUAWEI TECHNOLOGIES CO., LTD.

Advertisement

loading

Summary of Contents for Huawei FusionDC1000A

  • Page 1 FusionDC1000A Prefabricated All-in-One Data Center Quick Guide (2020, Nigeria, River) Issue Date 2020-11-30 HUAWEI TECHNOLOGIES CO., LTD.
  • Page 2 Notice The purchased products, services and features are stipulated by the contract made between Huawei and the customer. All or part of the products, services and features described in this document may not be within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements, information, and recommendations in this document are provided "AS IS"...
  • Page 3: About This Document

    Indicates a hazard with a low level of risk which, if not avoided, could result in minor or moderate injury. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 4 Change History Changes between document issues are cumulative. The latest document issue contains all the changes made in earlier issues. Issue 01 (2020-11-30) This issue is the first official release. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 5: Table Of Contents

    Contents Contents About This Document........................ ii 1 Quick Guide Usage........................1 2 Installation Drawings......................3 3 Removing Transport Protection Materials................ 4 4 Initial Configuration Parameters..................6 A Common Torque Selection Table..................7 Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 6: Quick Guide Usage

    This chapter describes the notes for using the quick guide. ● Before the installation, check whether the materials are intact according to the packing list. If there is any problem, contact Huawei technical support. ● This document provides only the initial configuration parameters required for data center commissioning and O&M as well as the drawings and parameters...
  • Page 7 Do not perform operations such as arc welding, drilling, and cutting on the top of a pre-fab. module. Table 1-1 Reference Documentation Item Document Name FusionDC1000A Prefabricated All-in-One Data Center FusionModu V100R021C00 Installation Guide (CT) FusionDC1000A Prefabricated All-in-One Data Center V100R021C00 Commissioning Guide (CT)
  • Page 8: Installation Drawings

    FusionDC1000A Prefabricated All-in-One Data Center Quick Guide (2020, Nigeria, River) 2 Installation Drawings Installation Drawings Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 9 Checklist of Devices Installed Onsite Installation Sequence Subcategory Item Diagram ID Diagram Name Installing Pre-fab. Module Bases Site Space And Pre-fab. Module Installation Installing Pre-fab. Modules (Base Solution) NO.S002 Removing the Pre-fab. Module Cover Position Diagram (Single-capacity Base Installing a Pre-fab. Module Scenario) Hoisting and Securing Pre-fab.
  • Page 15 No.P017 Power module installation position diagram The power module is installed in the position shown Find the UPS power module ( 02311NXM*2pcs ) from in the following figure. the packaged materials. Note : The position marked 2 is the power module installation position.
  • Page 16 No.P018 Lithium battery installation position diagram Find the UPS battery module ( 02311PCW*8pcs ) Remove the protective cover from the rear of the from the packaged materials. battery Removing the filler panel from the UPS. Push the battery module whose positioning lock is in unlocked state into the cabinet, and turn the positioning lock to the locked state.
  • Page 17 No.P011 Grounding System Wiring Diagram Air outlet window Air Conditioner-1 Air Conditioner-2 Air Conditioner-3 Air Conditioner-4 Air Conditioner-5 Air Conditioner-6 ( E C50 ) ( E C50 ) ( E C50 ) ( E C50 ) ( E C50 ) ( E C50 ) Main PDF Humidifier-1(Up Option)
  • Page 18 (25kVA*2) Battery WY-10A Socket-2 (12V/9Ah*2 组 ) Cable Relation Table Terminal Relation Table INPUT OUTPUT Power System Huawei Part Description Terminal Spec From Part 1 Terminal Spec From Part 2 Cable No. Breaker Container From Device Container To Device 14170215...
  • Page 19 (25kVA*2) Battery WY-10A Socket-2 (12V/9Ah*2 组 ) Cable Relation Table Terminal Relation Table INPUT OUTPUT Power System Huawei Part Description Terminal Spec From Part 1 Terminal Spec From Part 2 Cable No. Breaker Container From Device Container To Device 14170215...
  • Page 20 No.M004 Monitoring Device Installation Position Diagram Air outlet window Air Conditioner-1 Air Conditioner-2 Air Conditioner-3 Air Conditioner-4 Air Conditioner-5 Air Conditioner-6 WATER ( EC50 ) ( EC50 ) ( EC50 ) ( EC50 ) ( EC50 ) ( EC50 ) Water Sensor-1 Main PDF Humidifier-1(Up Option)
  • Page 22 No.F004 Fire Extinguishing Device Installation Position Diagram (CE) Air outlet window Air Conditioner-1 Air Conditioner-2 Air Conditioner-3 Air Conditioner-4 Air Conditioner-5 Air Conditioner-6 ( EC50 ) ( EC50 ) ( EC50 ) ( EC50 ) ( EC50 ) ( EC50 ) Main PDF Humidifier-1(Up Option) Connecting Cables to...
  • Page 23 No.P009 Wiring Diagram From The Mains To The Power PDF Air outlet window Air Conditioner-1 Air Conditioner-2 Air Conditioner-3 Air Conditioner-4 Air Conditioner-5 Air Conditioner-6 Main PDF ( E C50 ) ( E C50 ) ( E C50 ) ( E C50 ) ( E C50 ) ( E C50 ) Humidifier-1(Up Option)
  • Page 24: Removing Transport Protection Materials

    Securing tape and red cover Horn strobe Securing tape Fire alarm bell Securing tape Emergency light Securing tape T/H sensor Securing tape Camera Securing tape Emergency door release Plastic cover button Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 25: Initial Configuration Parameters

    FusionDC1000A Prefabricated All-in-One Data Center Quick Guide (2020, Nigeria, River) 4 Initial Configuration Parameters Initial Configuration Parameters Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 26 No.P001 Power Distribution Device Layout Air outlet window Air Conditioner-1 Air Conditioner-2 Air Conditioner-3 Air Conditioner-4 Air Conditioner-5 Air Conditioner-6 WY-10A Socket-1 (EC50) (EC50) (EC50) (EC50) (EC50) (EC50) Main PDF Humidifier-1(Up Option) Light-1 UPS5000E-B (25kVA*2) Battery WY-10A Socket-2 (12V/9Ah*2 组 )
  • Page 27 No.P002 Power Supply And Distribution System Diagram 50KVA UPS Battery Main PDF 600*300*2000 QF1 C100A/3P 1QF1 C40A/1P Rack1-rPDU-1 Battery LOCK QF2 C100A/4P 1QF2 C40A/1P Rack1-rPDU-2 QF3 C40A/1P 1QF3 C40A/1P Air Conditioner-1 Rack2-rPDU-1 QF4 C40A/1P 1QF4 C40A/1P In=30kA Air Conditioner-2 Rack2-rPDU-2 QF5 C40A/1P 1QF5 C40A/1P Air Conditioner-3...
  • Page 28 Table 1 Initial Configuration Parameters for Power Supply and Distribution Devices Device Name Project Configuration Quantity Power Distribution Device Name Remarks 8D ATS ■Involved □Not involved Main PDF Integrated UPS ■Involved □Not involved UPS5000E-B Note: The following device parameters are not all parameters of the devices. Only the parameters that need to be set for the project are listed. Default values will be used for the other parameters so they do not need to be set.
  • Page 29 Main PDF-1 Component ABB 8D ATS Initial Configuration Parameters Parameter Category Default Value Value Range Setting Remarks Password 0001 Default value 100/57 V-115/66 V-120/70 V-208/120 V-220/127 V-230/132 Rated Voltage 400/230 V V-240/138 V-277/160 V-347/200 V-380/220 V-400/230 V- 415/240 V 415/240 V-440/254 V-480/277 V Rated Frequency 50 Hz 50 Hz, 60 Hz...
  • Page 30 Parameter Category Default Value Value Range Setting Remarks Freq Threshold Min LN1 -10% to -1% Freq Threshold Min LN2 -10% to -1% Frequency Thresholds Freq Threshold Max LN1 +1% to +10% Freq Threshold Max LN2 +1% to +10% Freq Hysteresis Min LN1 -3.0% -9.8% to -0.8% -3.0%...
  • Page 31 UPS-1 Component Initial Configuration Parameters for Integrated UPS UPS5000-E-(25kVA-75kVA) Category Parameter Default Value Value Range Setting Remarks English, Chinese, Spanish, Dutch, French, German, Italian, Polish, Language English English Portuguese, Russian, Swedish, and Turkish. Date format YYYY-MM-DD YYYY-MM-DD Tester Settings YYYY-MM-DD XXXX-XX-XX XXXX-XX-XX Tester Settings...
  • Page 32 Category Parameter Default Value Value Range Setting Remarks Start addr.Of batt.temp.sensor 16—28 Default value BMUs Default value ≤12 BMU start address Default value Amb.temp & humid sensors Default value ≤4 Communication s Settings Start addr.Of batt.temp.& hum.sensors 32—44 Default value Disable Disable/Enable Default value...
  • Page 33 Category Parameter Default Value Value Range Setting Remarks Low ambient temperature alarm threshold (°C) Default value Top outlet fan Disable Enable EOD restart Enable Default value EOD restart delay (min) 1min—1440min Default value Inverter async. Alarm Disable Default value Bus overvoltage recovery Enable Disable/Enable Default value...
  • Page 34 Category Parameter Default Value Value Range Setting Remarks Output Param. Output volt. adjustment (V) Default value Screen Output freq. track rate (Hz/s) 0.1Hz/s—2.0Hz/s Default value Self-load output cur. ratio (%) 20%—100% Default value Output interruption transfer time (ms) Default value Max.
  • Page 35 Category Parameter Default Value Value Range Setting Remarks Scheduled equalized charging interval (d) Default value Float volt. temp. comp. Default value Float volt. temp. comp. coef. (mV/°C· cell) Default value Max. batt. dis. time (h) 16~48 Default value Sched. shallow dis. Test Default value Shallow dis.
  • Page 36 Category Parameter Default Value Value Range Setting Remarks SPD/SYSOUT Switch Disable Disable/Enable Default value MUS05A DO_1 Action Close Default value MUS05A DO_2 Action Close Default value MUS05A DO_3 Action Close Default value Dry Contact MUS05A DO_4 Action Close Default value Settings MUS05A DO_01 Critical alarm...
  • Page 38 Table 2 Initial Configuration Parameters for Cooling Devices Initial Temperature and Humidity Configuration Parameters for 5kw Cooling Product Air Conditioner Remarks CoolSP Band Air Conditioner-1 Air Conditioner-2 Air Conditioner-3 Password setting(Initial password: 0001) Air Conditioner-4 Air Conditioner-5 Air Conditioner-6...
  • Page 39 Fire door electric heater DICELL XR02CX thermostat initial configuration parameters Set Category Setting Item Default value Setting the threshold Factory Setting Remark Set Point -55 - 99 ℃ 15℃ Differential 2.0°C 0.1 - 25 °C 5°C Anti-short cycle delay 0 - 50 min Adjusting Parameters Compressor ON time faulty probe 0 - 99 min...
  • Page 40 Humidifier Initial Configuration Parameters (Optional) Item Default Value Setting Maximum vapor generation amount Humidifier deviation Maximum sensor threshold Minimum sensor threshold Outlet setting Operating mode Unit of measurement Steam generation request signal type Minimum room sensor Maximum room sensor...
  • Page 41 No.M001 Monitoring Device Layout Diagram Air outlet window Air Conditioner-1 Air Conditioner-2 Air Conditioner-3 Air Conditioner-4 Air Conditioner-5 Air Conditioner-6 WATER ( EC50 ) ( EC50 ) ( EC50 ) ( EC50 ) ( EC50 ) ( EC50 ) Water Sensor-1 Main PDF Humidifier-1(Up Option) IP Camera-1...
  • Page 42 No.M002 Monitoring System Network Diagram Main PDF_SPD1 Main PDF_SPD2 Water Sensor-1 Reserved ECCE-1 Reserved Reserved Reserved Reserved Reserved Reserved T&H-1 LOCAL FIRE FAULT RELAY ECC800 BACK Collector_ECC800-1 Reserved FIRE RELAY Main PDF_METER Main PDF_ATS Reserved Smart ETH Gateway-3 Smart ETH Gateway-2 Smart ETH Gateway-1 PWR_IN PWR_OUT...
  • Page 43 Table 3 Initial Configuration Parameters for the Management System WebUI Port to Upper- Device LCD User Upper- Monitoring Data Device Device Device Device Alarm User Name Upper- Level Name and Transfer Level Remarks Device Type Code Name Model Address Threshold Level Device Address...
  • Page 44 WebUI Port to Upper- Device LCD User Upper- Monitoring Data Device Device Device Device Alarm User Name Upper- Level Name and Transfer Level Remarks Device Type Code Name Model Address Threshold Level Device Address Password Port Device Password Devic Port Collector_ECC Smart ETH Collector_E...
  • Page 45 WebUI Port to Upper- Device LCD User Upper- Monitoring Data Device Device Device Device Alarm User Name Upper- Level Name and Transfer Level Remarks Device Type Code Name Model Address Threshold Level Device Address Password Port Device Password Devic Port User name: Admin Collector_ECC...
  • Page 46 WebUI Port to Upper- Device LCD User Upper- Monitoring Data Device Device Device Device Alarm User Name Upper- Level Name and Transfer Level Remarks Device Type Code Name Model Address Threshold Level Device Address Password Port Device Password Devic Port Collector_ECC Main Password:...
  • Page 47 No.F001 Fire Extinguishing Device Layout Diagram (CE) Air outlet window Air Conditioner-1 Air Conditioner-2 Air Conditioner-3 Air Conditioner-4 Air Conditioner-5 Air Conditioner-6 ( EC50 ) ( EC50 ) ( EC50 ) ( EC50 ) ( EC50 ) ( EC50 ) Main PDF Humidifier-1(Up Option) UPS5000E-B...
  • Page 48 No.F002 Fire Extinguishing System Conceptual Diagram (CE) - 1 Horn Strobes-2 Horn Strobes-1 Terminal Resistor - + + - + + Warning Signs-1 Terminal Resistor Terminal Resistor 6.8K 6.8K COMM+LEV1 LEV2 2WIRE SILENCE COMM+ LEV1 LEV2 2WIRE SILENCE Terminal Resistor Pneumatic switch-1 6.8K Fire Alarm Bell-1...
  • Page 49 No.F002 Fire Extinguishing System Conceptual Diagram (CE) - 2 Smoke Detector-1 L1 IN Terminal Resistor ( 6.8K ) L1 OUT black Heat Detector-1 L1 IN Terminal Resistor ( 6.8K ) L1 OUT black To Monitoring system green brown green brown green brown &...
  • Page 50 No.F002 Fire Extinguishing System Conceptual Diagram (CE) - 3 Main PDF OVDC QF11 YO(OF) 24VDC black black DATA POWER ZONE 1 ZONE 2 ZONE 3 FAULT LOCAL FIRE MODE HOLD EXTING EXTRACT REMOTE RELEASE PRESS SOUNDER STAGE STAGE SELECT PRESS RELAY FIRE RELAY...
  • Page 51 No.L001 Lighting Device Layout Diagram Air outlet window Air Conditioner-1 Air Conditioner-2 Air Conditioner-3 Air Conditioner-4 Air Conditioner-5 Air Conditioner-6 WY-10A ( E C50 ) ( E C50 ) ( E C50 ) ( E C50 ) ( E C50 ) ( E C50 ) Socket-1 Main PDF...
  • Page 52 No.F003 Emergency Exit Diagram Air outlet window Air Conditioner-1 Air Conditioner-2 Air Conditioner-3 Air Conditioner-4 Air Conditioner-5 Air Conditioner-6 ( EC50 ) ( EC50 ) ( EC50 ) ( EC50 ) ( EC50 ) ( EC50 ) Main PDF Humidifier-1(Up Option) UPS5000E-B (25kVA*2) Battery...
  • Page 53: A Common Torque Selection Table

    Block Battery (Commo Wiring n Steel Terminal Connecto Cross Electric recessed screwdriv small pan head screw assembly Cross Electric recessed screwdriv counters unk head screw; cross recessed pan head screw assembly Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 54 Cross Pneumati recessed counters screwdriv unk head screw Hexagon Torque head wrench screw assembly Hexagon Torque head wrench screw assembly Common Torque 1600 1200 bolt wrench Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 55 50 (for recessed checking, hexagon screwdriv not for flange tightenin self- drilling tapping screw G1/2'' 1/2'' pipe Torque connecto wrench G3/4'' 3/4'' pipe Torque connecto wrench G1'' 1'' pipe Torque connecto wrench Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.