3. Receiving the product

WARNING
Crushing of feet
Death or serious personal injury
- Use safety shoes during transport and avoid
stacking the boxes.
CAUTION
Heavy lifting
Minor or moderate personal injury
- Use proper lifting equipment when handling the
product.
- Follow local regulations.

3.1 Transporting the product

To prevent damage during the transport, CUE must only be
unpacked at the installation site.

3.2 Inspecting the product

Check on receipt that the packaging is intact and the unit is
complete. In case of damage during transport, contact the
transport company to complain.
Note that CUE is delivered in packaging which is not suitable for
outdoor storage.

3.3 Scope of delivery

The packaging contains one or more accessory bags,
documentation and the unit itself. See fig. 2.
Documentation
Accessory
bags
Fig. 2
CUE packaging
3.3.1 Lifting CUE
Always lift the product using the lifting holes. Use a bar to avoid
bending the lifting holes. See fig. 3.
Fig. 3
Recommended lifting method
4

4. Installation requirements

Any installation, maintenance and inspection must be
carried out by trained persons.
WARNING
Sharp element
Death or serious personal injury
- Use safety knives and protective gloves when
unpacking the product.
WARNING
Heavy lifting
Death or serious personal injury
- Use proper lifting equipment when handling the
product.
- Follow local regulations.
WARNING
Electric shock
Death or serious personal injury
- Before starting any work on the product, make
sure that the power supply has been switched off
at least for as long as stated below and that it
cannot be accidentally switched on.
- Touching the electrical parts may be fatal, even
after CUE has been switched off.
Voltage
4 minutes
0.75 - 3.7 kW
200-240 V
(1-5 hp)
0.55 - 7.5 kW
380-500 V
(0.75 - 10 hp)
0.75 - 7.5 kW
525-600 V
(1-10 hp)
525-690 V
Only wait for a shorter period of time if stated on the nameplate of
the product in question.
Safety regulations
The OFF button of the operating panel does not disconnect
CUE from the power supply and must therefore not be used as
a safety switch.
CUE must be earthed correctly and protected against indirect
contact according to local regulations.
The leakage current to protective earth exceeds 3.5 mA.
Enclosure class IP20/21 must not be installed freely
accessible, but only in a panel.
Enclosure class IP54/55 must not be installed outdoors
without additional protection against weather conditions and
the sun.
The STO function does not disconnect CUE from the power
supply and must therefore not be used as a safety switch.
The STO function does not prevent unwanted movement from
external forces on the motor, for example, back pressure, and
the motor shaft must be covered.
Always observe local regulations concerning cable cross-section,
short-circuit protection and overcurrent protection.
Min. waiting time
15 minutes
20 minutes
5.5 - 45 kW
(7.5 - 60 hp)
11-90 kW
110-250 kW
(15-125 hp)
(150-350 hp)
11-250 kW
(15-350 hp)