8. Control functions
The display contrast can be adjusted by pressing
[Status] and then pressing [Up] or [Down].
8.1 Operating panel
The operating panel consists of a display and several buttons. It
enables manual setting and monitoring of the system, such as
follows:
•
Start, stop and control of speed.
•
Reading of operating data and warnings and alarms.
•
Setting functions for the frequency converter.
•
Manual reset of the frequency converter.
21
Status
799 RPM
20
53.2 %
19
Auto Remote Ramping
18
17
16
On
15
Warn.
14
Alarm
13
Hand
Off
on
12
11
Fig. 51 Operating panel
Pos.
Buttons
Description
1
Power [kW]
2
Reference [%]
[Alarm log]: shows a list of current
3
warnings, the last 10 alarms and the
maintenance log.
[Main menu]: allows access to all
4
programming settings.
[Cancel]: cancels the last change or
5
command as long as the display mode
has not changed.
[Info]: press for a definition of the
6
function being displayed.
[Up]/[Down]/[Left]/[Right]: use the four
7
arrow buttons to navigate between items
in the menu.
[OK]: used to access parameter groups
8
or to accept a selection.
[RESET]: resets the frequency converter
9
RESET
manually after a fault has been cleared.
[AUTO ON]: puts the system in remote
operational mode.
10
• Responds to an external start
AUTO
ON
command by control terminals or serial
communication.
[OFF]: stops the motor but does not
11
remove power to the frequency
OFF
converter.
[HAND ON]: starts the frequency
converter in local control.
12
• An external stop signal by control input
HAND
ON
or serial communication overrides the
local [Hand On] function.
20
1
1(1)
7.83 A
36.4 kW
0.000
2
3
4
5
6
7
Auto
Reset
on
8
10
9
Pos.
Buttons
Description
A fault condition causes the red alarm
[Alarm]
13
light to flash and an alarm text is
Red
displayed.
When warning conditions are met, the
[Warn.]
yellow warning light comes on and text
14
Yellow
appears in the display area identifying
the problem.
The On light activates when the
[On]
frequency converter receives power from
15
Green
the mains voltage, a DC bus terminal or
an external 24 V supply.
[Back]: reverts to the previous step or list
16
in the menu structure.
[Favourites]: allows access to
programming parameters for initial set-
17
up instructions and many detailed
application instructions.
18
[Status]: shows operational information.
19
Frequency
20
Motor current
21
Speed, RPM
8.2 Menu overview
Overview of the main menus. The ** represents a number to a
submenu.
•
"0-** Operation / Display"
•
"1-** Load and Motor"
•
"2-** Brakes"
•
"3-** Reference / Ramps"
•
"4-** Limits / Warnings"
•
"5-** Digital In/Out"
•
"6-** Analog In/Out"
•
"8-** Comm. and Options"
•
"14-** Special Functions"
•
"15-** Drive Information"
•
"16-** Data Readouts"
•
"18-** Info & Readouts"
•
"20-** Drive Closed Loop"
•
"21-** Ext. Closed Loop"
•
"22-** Appl. Functions"
•
"23-** Timer-based Functions"
•
"27-** Cascade CTL Option"
•
"29-** Water Application Functions"
•
"30-** Special Features"
•
"35-** Sensor Input Option"
•
"200 - Operation Settings"
•
"201- Key Functions"
•
"202 - Sensors"
•
"203 - Status Monitor"
Example: To get to the menu "1-28 Motor Rotation Check", you
must do the following:
1. navigate to "1-** Load and Motor", and press [OK].
2. Use the [Up] and [Down] buttons to navigate to "1-2* Motor
Data", and press [OK].
3. Use the [Up] and [Down] buttons to navigate to "1-28 Motor
Rotation Check", and press [OK] to select the menu.