2.13

Installing the controller

Type CC 60-H2-M1
Biddle bv
Code
xxx
Markowei 4
Nº 123456/1-1 05-53
NL-9288 HA Kootstertille
M 30 kg
Medium LPHW
p
1400 kPa
max
Version: 1.0 (22-09-2005)
2.13.1 Controller details
Positioning
Cabling
n
n
Multiple units operated from one controller
code
U 230 V 1N~ 50 Hz
I
L1 xxx A
max
I
L2 -
max
I
L3 -
max
P
xxx kW
motor
P
-
heating
Fix the controller to the wall or to a standard socket.
Mount the controller at a height of 1.5 m above the floor.
Note:
Take the following into account, otherwise faults may
occur:
-
The control cable between the controller and the
(first) connected unit is not to exceed 50m.
-
Keep control cables away from electromagnetic fields
and interference sources such as high-voltage cables
and fluorescent-light starters.
-
Stretch control cables out or wind them bifilarly.
Note:
Use only control cables from Biddle Biddle. Standard mod-
ular telephone cable is not suitable.
Up to 10 units can be connected to one single controller.
To do so, the units must be interlinked.
The following combinations of units are possible:
-
units with unit codes ending on 11;
-
units with unit codes ending on 21;
-
units with unit codes ending on 12, 13 or 14;
-
units with unit codes ending on 22, 23 or 24;
-
unit code 3000 only in conjunction with code 2023.
The total length of the control cables is not to exceed
100 m.
The distance between the controller and the first unit is
not to exceed 50 m.