Biddle Comfort Circle Series Manual page 32

Table of Contents

Advertisement

S
ETTINGS
N
.
F
O
UNCTION
50
Reset settings
This allows you to reset all settings in the
installation menu and timer menu to their
default values.
51
Maximum filter life
52
Ignore fault code F1
55
Adjusting controller's temperature reading
Use this function if the displayed room temper-
ature differs from the actual temperature.
56
Night temperature
57
Minimum discharge temperature, heating
58
Minimum discharge temperature, cooling
59
Dead band for switching between heating and
cooling (CC S and M)
This is also used for switching off the fan in the
mode (CC M)
AUTO
61
Dead band around temperature setpoint for
heating (CC S)
62
Dead band around temperature setpoint for
cooling
64
PID factors of temperature control
64.0
64.5
70
From speed 1 to speed 2 when heating
70.5
From speed 2 to speed 3 when heating
71
From speed 1 to speed 2 when cooling
71.5
From speed 2 to speed 3 when cooling
72
Time-based speeding-up, heating
73
Time-based speeding-up, cooling
74
Minimum running time at a fan speed
32
Table 3-1 Functions in the installation menu
O
PTIONS
df
= all functions have default values
__
= there are functions with deviating values
To reset:
+
• press
and
Presettable between 1 and 51 weeks(26)
0 = show fault code (default)
1 = ignore fault code
Can be set between -3 and +3°C (0°C)
Can be set between 5 and 30°C (15°C)
Can be set between 12 and 55°C (22°C)
Can be set between 12 and 30°C (12°C)
Can be set between 1 and 5°C (1.5°C)
Can be set between 0.5 and 4°C (0.8°C)
Can be set between 0.5 and 1.0°C (0.8°C)
Do not change these settings, unless on Biddle's
instructions.
1-5, Off (1.5)
This is the difference between the temperature
setpoint and the room temperature where the
unit operating in the
over to another speed. For speed 2 to speed 3,
the value of speed 1 to speed 2 must be added
to the value.
0 = Off
1 = On (default)
If the temperature setpoint is not reached
within a specified period of time, the fan will
start rotating one speed higher. If the tempera-
ture is not reached within a specified period of
time, the fan will start rotating one speed lower
again.
1-5 minutes, Off (Off)