Sensor data
Approval
VDE approval pending-VDE according to
EN60730 EMC According to EN 50081-1/2
for emission and EN50082 - 1/2 for immunity
Temperature for bal pressure +100°Ctest
(DIN EN 60730/VDE 0631-1)
Rated impulse voltage: Overvoltage category III
(DIN EN 60730/ VDE 0631-1)

4. OPERATION

The Raystat V5 has a LED user screen interface:
The unit will switch to the main screen after 2 minutes of non-interaction on the
parameter input screens.

4.1 Quick install

When the unit is powered up for the first time, a quick setup must be executed before
the unit is ready to start. The Quick start helps to set all important settings, the
unit will go in main screen mode automatically when done. Quick start is sufficient
for normal operations. More settings are available in the Setup menu for special
installation conditions.
The Quick start will only start if no pre-setting is done.
The parameters can be changed by pressing the check mark button for 6 sec.
The controller can be protected by a keylock. If this keylock function is active, the
code (see SP 12 in parameter list) needs to be entered to unlock the unit. Resetting
the Raystat V5 to factory settings is done by simultaneously pressing the arrow up,
down arrow and OK buttons for 6 seconds.
10 | nVent.com
Temperature
Resistance in kOhm
–40°C
32,34
–35°C
24,96
–30°C
19,48
–25°C
15,29
–20°C
12,11
–15°C
9,655
–10°C
7,763
–5°C
6,277
0°C
5,114
+5°C
4,188
+10°C
3,454
+15°C
2,862
+20°C
2,387
+30°C
1,684
+40°C
1,211
+50°C
0,8854
+60°C
0,6587
+70°C
0,4975
+80°C
0,3807

Parameter overview :

Operation
Operation
PARAMETER
Mode:
Mode:
LINE
PASC
SP1
SP2
SP3
SP4
SP5
SP6
SP7
SP8
SP9
SP10
SP11
SP12
Error codes :
Error
Error
Code
description
1. Check sensor cable connection
Er 2.1 Sensor open
2. Verify operation of unit
3. Replace unit if cable ok & error still exists
1. Check sensor connection
Er 2.2 Sensor short
2. Replace sensor
3. Replace unit if sensor ok & error still exists
Low
1. Verify heating system and sensor position
Er 3.1
temperature
2. Verify menu settings of high temperature alarm
alarm
High
1. Verify heating system and sensor position
Er 3.2
temperature
2. Verify menu settings of high temperature alarm
alarm
Heating cable
Er 5.0
Verify heating cable connection
disconnected
Er 6.0 Internal error
Replace unit
Factory
Description
settings
SET Temperature
+3°C
Operation mode selection
-----
Lowest ambient
-20°C
temperature
Average pipe diameter
2
level
>= DN 25 / 1"
Heater operation in
ON
sensor failure mode
Heater operation via
No
external contactor
Hysteresis
1 K
Low temperature alarm
0°C
Higher temperature alarm
+65°C
Alarm sound status
ON
TEST program
OFF
KEY LOCK – Pass code
OFF
Remedy
nVent.com | 11