• Do not tighten the screws with too much force, since it can damage
the PS-A unit's.
• The torque necessary to create a drip-resistant seal is 0.5 N•m.
• Depending on the installation panel's thickness, etc., the number of installa-
tion fasteners used may need to be increased to provide the desired level of
moisture resistance.
• Be sure to use installation fastener model CA3-ATFALL-01.

Attach the PS-A unit to an Arm

To attach the PS-A unit to an Arm or to the wall, insert the attachment screws for a
commercial-type arm or wall mount adaptor into the holes in the PS-A's rear face.
(Holes specifications: VESA 75mm)
For detailed attachment instructions, please refer to that product's installation
guide.The VESA Arm Attachment Hole dimensions are signifies as follows;
Attach the four (4) M4 attachment screws. (Screw length : 6mm or less.) The torque
required for these screws is 0.7 to 0.8 N.m.
75[2.95]
Rear Face
(unit: mm[in.])