(RS-422)
Pin No.
Signal
1
RXA
2
RXB
3
TXA
4
NC
5
GND
6
NC
7
TXB
8
NC
9
NC
FG
FG
(RS-485)
Pin No.
Signal
1
DATE+
2
DATE-
3
NC
4
NC
5
GND
6
NC
7
NC
8
NC
9
NC
FG
FG
• Be sure to connect pin number 5 (SG) of COM1 to the host unit's
Signal Ground terminal.
• Be sure to confirm what settings will be used by the other
device and set the dip switches accordingly. Failure to do so can
result in a unit malfunction or damage.
• Whenever changing the PS-A switches, be sure to first turn the
PS-A's power supply OFF. Failure to do so can cause a PS-A
malfunction.
• Connect the FG terminal line to the connector cover's PS-A con-
nector attachment screw.
• FG and SG terminals are internally connected in the PS-A. When
connecting to another device, be sure to create an SG shorting
loop in your system.
Use inch type (#4-40UNC) threads to hold the cable's set (attachment) screws
in place.
Signal Name
Receive Data (+)
Receive Data (-)
Send Data (+)
No Connection
Ground
No Connection
Send Data (-)
No Connection
No Connection
Frame Ground
Signal Name
Send/Receive Data (+)
Send/Receive Data (-)
No Connection
No Connection
Ground
No Connection
No Connection
No Connection
No Connection
Frame Ground
Direction
Input
Input
Output
-
-
-
Output
-
-
-
Direction
In/Output
In/Output
-
-
-
-
-
-
-
-
E-11